Nominal Airflow 4700 m3/h
Entering Water Temp. (°C)
Water flow (l/s)
Water Pressure Drop (kPa)
Cooling mode
TEA (°C)
TSE (°C)
Pt (W)
Ps (W)
Pabs (W)
CR (W)
EER
32
1.35
55
24/17
36.6
20142
16726
5560
25702
3.62
27/19
36.9
21313
17888
5617
26930
3.79
30/21
37.3
23115
19030
5691
28806
4.06
1.01
33
24/17
38.1
19846
16526
5629
25475
3.53
27/19
38.7
21691
17958
5753
27444
3.77
30/21
39
22716
18975
5804
28520
3.91
0.68
14
24/17
41.3
19683
16588
5892
25575
3.34
27/19
42
21263
17863
6007
27270
3.54
30/21
42.5
22427
18799
6093
28520
3.68
38
1.35
55
24/17
42.6
19231
16287
6293
25524
3.06
27/19
42.9
20431
17497
6368
26799
3.21
30/21
43
21200
18398
6382
27582
3.32
1.01
33
24/17
43.7
18127
15854
6246
24373
2.90
27/19
44.6
20743
17533
6503
27246
3.19
30/21
44.9
21695
18719
6570
28265
3.30
0.68
14
24/17
47.2
18756
16134
6601
25357
2.84
27/19
47.4
19615
17136
6657
26272
2.95
30/21
48.2
21454
18570
6842
28296
3.14
40
1.35
55
24/17
44.5
18938
16256
6506
25444
2.91
27/19
44.9
20399
17483
6632
27031
3.08
30/21
45.1
21342
18495
6692
28034
3.19
1.01
33
24/17
45.7
17806
15643
6491
24297
2.74
27/19
46.6
20134
17483
6758
26892
2.98
30/21
46.6
20703
18101
6783
27486
3.05
0.68
14
24/17
49.3
18810
16018
6882
25692
2.73
27/19
49.4
19405
17009
6920
26325
2.80
30/21
50.3
20952
18279
7124
28076
2.94
45
1.35
55
24/17
49.6
18013
15952
7194
25207
2.50
27/19
49.6
18748
16889
7224
25972
2.60
30/21
49.9
20071
18040
7318
27389
2.74
1.01
33
24/17
51.1
17843
15835
7293
25136
2.45
27/19
51.4
19222
17056
7398
26620
2.60
30/21
51.5
19767
17850
7450
27217
2.65
0.68
14
24/17
54
17533
15627
7481
25014
2.34
27/19
54.1
18365
16642
7544
25909
2.43
30/21
54.8
19742
17840
7745
27487
2.55
TEA : Entering air temperature (dry bulb/wet bulb). Ps : Sensible cooling capacity.
TSE : Leaving water temperature. Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.

pageCatalog pdf di En 2012-06-22-01