| Refrigerant circuit (continued)_ The refrigerant circuit also comprises an HP pressure switch with manual reset (range 28-20 bar) and an LP pressure switch with an automatic reset function (range 1.4-2.4 bar). Two Shrader valves (HP & LP) are available for pressure measurement on the refrigerant circuit or on the front side of models 007 to 012. The water/refrigerant heat exchanger is of the brazed stainless steel plate type, for increased efficiency. The anti-freeze safety of the heat exchanger is provided by a water pipe sensor located on the water outlet of the unit monitored by the electronic board. Maximum service pressure on the water side (27.5 bar) and on the refrigerant side (28 bar). The heat exchangers are particularly well adapted to the operation of reversible heat exchangers which have high thermal transfer rates for a low water flow-rate. The air/refrigerant coil is made up of aluminium fins which are mechanically crimped onto copper tubes. The geometry of the coil and of the fin profile have been carefully designed to provide maximum efficiency in the operation of the units. The cycle reversal valve is designed to be normally energised in heating mode. This logic enables the heat pump to continue to operate in cooling mode if this valve fails. The liquid receiver enables the charge of HFC 407C refrigerant to be optimised, particularly in cooling mode, in order to maintain a high COP value. A Bi-Flow expansion valve ensures and enables a wide operating range with water inlet temperatures which can vary between 13 °C and 45 °C at the minimum or maximum flow-rate. Ventilation section_ The fan compartment contains the fan-motor assembly, the air/ refrigerant coil and the condensate drain pan. The ventilation section is completely isolated from fan compartment by a thermally and acoustically insulated partition wall. Wide removable panels provide access to the various internal components. The condensate drain pan has an anti-corrosion treatment and comprises a float-type safety device to prevent accidental overflow of the pan. All the units up to model 72 are equipped with a 3 speed direct-drive fan motor with ipsothermal protection against overheating during operation. The motor ipsothermal protection fault is displayed in the form of a coded signal on the LED of the RCL remote control. The 3 fan speeds can be controlled either manually or automatically by the electronic management board of the unit. The fan-motor assembly is mounted on an independent chassis which is isolated from the casing by anti-vibration mounts. Belt type drive with variable pitch pulley is supplied on models 096 and 120. In the standard configuration, the fan blows straight in line with the air intake. The perpendicular blowing option is available on all units by switching the side panels and the fan-motor assembly. Suspension kit_ In order to facilitate installation on site, a suspension kit consisting of rubber blocks and washers is supplied with the units (except for models 096 and 120). Optional features (factory installed) - Wired main disconnect switch to be installed on the casing (for models 019 to 120 only), - Electric heater at discharge side, - General alarms fault report, - Electrical connection kit (for models 007 to 012 only), - Compressor jacket (for models 007 to 012 only), - Motorized water valve (for models 019 to 120 only), - Return plenum (for models 007 to 012 only). |