Specifications Cont. Operator Interface

Temperature and Power Controllers catalog - 7347 Auto-Tuning PIDControllers

Allowable Operating Range •Dual 4 digit, 7 segment LEDdisplays•Advance, infinity and up downkeys•Optional IrDA infrared port (notavailable on Type J:0to815°C(32to1500°F)Type K:-200to1370°C(-328to2500°F)Type T:-200to400°C(-328to750°F)Type N:0to1300°C(32to2372°F)Type E:-200to800°C(-328to1470°F)Type C:0to2315°C(32to4200°F)Type D:0to2315°C(32to4200°F)Type PTII:0to1395°C(32to2543°F)Type R:0to1760°C(32to3200°F)Type S:0to1760°C(32to3200°F)Type B:0to1816°C(32to3300°F)RTD (DIN):-200to800°C(-328to1472°F)Process:-1999to 9999 units

SD_C

Accuracy •Calibration accuracy and sensor conformity: ±0.1 percent of span, ±1°C @ the calibrated ambient temperature and rated line voltage•Calibration ambient temperature = 25°C ±3°C (77°F ±5°F) •Accuracy span: 540°C (1000°F)minimum•Temperature stability: ±0.1°C/°C(±0.2°F/°F) rise in ambient maximum
1 â„
32 DIN)•Isolated EIA-485 Modbus™ serialcommunications. 9600,19.2K or 38.4K baud rates Agency Approvals Wiring Termination -Touch SafeTerminals •UL •Input power and control outputs12 to 22 AWG•Sensor inputs and processoutputs 20 to 28 AWG Universal Input •Thermocouple, grounded orungrounded sensors•RTD 2- or 3-wire, platinum, 100
® 3121, C-UL
® ‚ CSA, CE,NEMA 4X/IP65•Limit version features FM approval •NSF for Type J, K, T and Ethermocouples Ω / Ω /°C)•Process, 0-20mA @ 100 Ω @ 0°C calibration to DIN- curve (0.00385 Ω , or 0-10V Control OutputsOutputs 1, 2 , 3 (Output 3 notavailable on Controller Î (dc) @ 20k Ω inputimpedance; Scalable•Inverse scaling•>20M •Microprocessor based user-selectable control modes•Single universal input, up to threeoutputs•Control sampling rates: Input = 6.5Hz, Display = 10Hz, and Outputs = 6.5Hz Ω input impedance•Maximum of 20 Ω sourceresistance
1 â„
32 DIN) •User selectable for heat/cool ason-off, P, PI, PD, PID or Alarm action. Not valid for limit controls•Electromechanical relay. Form A,rated 2A @ 120V Å (ac), 2A @240V Dimensions Å (ac) or 2A @ 30V Î (dc)•Switched dc non-isolatedminimum turn on voltage of 6V Î (dc) into a minimum 500 Ω
DIN SizeBehind PanelWidthHeight(max.) load with a maximum on voltageof not greater than 12V
1 â„ 32 DIN97.8 mm52.6 mm29.7 mm(3.85 in.)(2.07 in.)(1.17 in.) Î (dc) intoan infinite load. Maximum switched dc power supply current available for up to two outputs is 60mA•Solid state relay, Form A, 0.5A @24V Å (ac) minimum, 264V Å (ac)maximum, opto-isolated, withoutcontact suppression
1 â„ 16 DIN97.8 mm52.1 mm52.1 mm(3.85 in.)(2.05 in.)(2.05 in.) 1 â„ 8 DIN97.8 mm52.8 mm99.8 mmVertical(3.85 in.)(2.08 in.)(3.93 in.) 1 â„ 8 DIN97.8 mm99.8 mm52.8 mmHorizontal(3.85 in.)(3.93 in.)(2.08 in.) 1 â„ 4 DIN101.1 mm99.8 mm99.8 mm(3.98 in.)(3.93 in.)(3.93 in.) 30