The small basic unit supplies a steam capacity of 1 to 4 kg/h ei­ther via a built-in ventilation de­vice for direct room humidification or with a steam nozzle/distribution pipe for duct application. An op­tional capacity display including a continuous control can also be built in.
The medium-sized basic unit per­mit steam production from 5 to 8 kg/h or from 9 to 15 kg/h, depending on the cylinder type. The steam is distributed by means of the Condair FAN ventilation unit or by steam distribution pipes. The devices can be supplemented by the optional M3 or M4 modules.
The large basic unit generates 16 to 25 kg/h or 26 to 45 kg/h, depending on the cylinder type. Higher steam capacities of up to 360 kg/h are built up using "slave" units. Steam is introduced into the room by the Condair FAN or via steam distribution pipes into duct systems. M3 or M4 modules are optional available.
Equipment models
Basic units Steam capacity Module
Humidity control Controller type
medium
5-8
M3/M4
Contr. int./external continuous 2)/ quasi-continuous
medium
9-15
M3/M4
Contr. int./external continuous 2)/ quasi-continuous
large
16-25
M3/M4
Contr. int./external continuous 2)/ quasi-continuous
large
26-45 M3/M4
Contr. int./external continuous 2)/ quasi-continuous
small
1-4
M 1)
Hygrostat
continuous 2)/on-off
1) cannot be retrofited
2) only with built in module
Technical data subject to modification
Consulting, Sales and Service:
Reg. No.40002-2
Manufacturer:
Axair Ltd. Systems for Air treatment
A WMH Company |
CH-8808 Pfàffikon (Switzerland), Talstr. 35-37, P. O. Box Tel. +41 55 416 61 11, Fax +41 55 416 62 62
LU
CD
LO
Internet http://www.axair.ch, e-mail info@axair.ch
condair
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
pdf-page pdf di En 2008-10-41-08