Hitachi RCI 4-Way Cassette - Walter Meier (Klima International) AG - #1

/ 1


catalogue search
Hitachi RCI 4-Way Cassette - Walter Meier (Klima International) AG
P. 01
Page:
Hitachi RCI 4-Way Cassette - Walter Meier (Klima International) AG


See other catalogues for Walter Meier (Klima International) AG

Text version of the page
HITACHI 4-WAY CASSETTE UTOPIA
HITACHI 4-WAY CASSETTE UTOPIA
RCI 4-WAY CASSETTE
Quiet operation
Compact and lightweight
Easy installation and maintenance
■ Slim air panel
■ Improved piping
■ Drain pump as standard
■ New DC fan motorfor increased efficiency
■ High ceiling adaptability
■ 7 day timer
Cooling kW 5.00 to 14.00 Heating kW 5.60 to 16.00
R410A refrigerant
llnrfuor Unit Technical Data
RCI-4FSN1E
F!C;-SFSNiL;
RC1-6FSN1E
Cooling (kW) - Nominal
10.00
12.50
14,00
Heating (kW) - Nominal
11.20
14.00
16.00
Cooling (kW)-UK Condition
10.54
13.40
16.75
Heating (kW)-UKCondition
12.55
16.21
17.47
Sensible Heat Ratio (SHR)
0.78
0.74
0.73
Sound Pressure Level (dBA)
38/35/33
39/37/35
42/40/36
Height - mm (Grille)
298(37)
298 (37)
298 (37)
Width-mm (Grille)
840 (950)
840 (950)
840 (950)
Depth - mm (Grille)
840 (950)
840 (950)
840 (950)
Weight-kg (Grille)
26(6)
26(6)
26 (6)
Air Flow Rate (m'/mln)
32/28/24
34/29/25
37/32/27
1 uuianor unii iccnnico* Uala —
RAS-4HRNE
RAS-SHRNf
RA5-6HRNE
Height (mm)
1240
1240
1240
Width (mm)
950
950
950
Depth (mm)
315
315
31S
Weight (kg)
100
102
102
Airflow (m'/mln)
so
90
100
Sound Pressure (dBA)
45
47
48
Sound Pressure -Set Back (dBA)
41
43
44
Uquld-mm (inches)
9.S2 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas - mm (inches)
IS.88 (5/8)
15.88(5/8)
15.88 (5/8)
Max Pipe Run (m)
77
77
77
Max Pipe Lift(m)
30
30
30
Pre-charged to(m)
30
10
30
Standing Charge (kg)
3.6
3.6
3.6
Refrigerant
R410A
R410A
R410A
Phase
Three
Three
Three
Power Supply to
Outdoor *
Outdoor*
Outdoor '
Max Current (A)
11
15
15
Fuse Rating (A)
16
16
16
Interconnecting
LNE + 2'
LNE + 2-
LNE + 2-
H-Link Compatible
Yes
Yes
Yl'S
Enerpy feet*
ECA Approved
Energy Rating (Cool/Heat)
Yes A/A
Yes A/A
Yes A/A
EER
3.85
3.49
3.19
COP
4.39
4.12
3 78
' Note: Power can be supplied either from outdoor unit (via local fused isolator) or separately. Interconnecting wiring
should be LNE + 2 core screened comms cable if mains
power ˇ5 to outdoor unit only or 2 core screened comms cable only if power supply isto both indoor and outdoor units.
Operating Conditions
Nom. Cool
Norn. Heat
UK. Cool U.K.Heat
Indoor Air Inlet Temperature
DB
27.00
20.00
23,00 22.00
W8
19.00
16.00
Outdoor Air Inlet Temperature
DB
35.00
7.00
30,00
Itidoot Unii Technical Ditta
RCI-2FSN1F
RCI-2.5FSN1E
RG-3FSN1E
RCI-4FSN1E
RCI-5FSN1E
Cooling (kW) - Nominal
5.00
6.30
7.10
10.00
12.50
Heating (kW) ■ Nominal
5.60
7.00
8.00
11.20
14.00
Cooling (kW) - UK Condition
5.35
5.92
7.5-1
10.54
13.40
Heating (kW)- UK Condition
6.30
6.15
8.89
12.SS
16.21
Sensible Heat Ratio (SHR)
0.78
0.73
0.79
0.78
0,74
Sol.nd Pressure Leve (dBAj
32/30/28
32/30/28
34/32/30
38/35/33
39/37/35
Height ■ mm (Grille)
248 (37)
248 (37)
298 (37)
298(37)
298 (37)
Width • mm [Grille)
840 (950)
840 (9S0)
840 (950)
840 (950)
840 (950)
Depth-mm (Grille)
340 (9 SO)
840 (950)
840 (950)
840 (950)
840 (950)
Weight ■ kg {Grille)
24 (6)
2d (61
26(6)
26(6)
26(6)
Air Flow Rate (mVmin)
16/14/12
20/17/15
26/23/20
32/28/2'-
34/29/25
1 Outdoor Unit Technical Data 1
Model
RAS-2HVRN1
S!AS-2.SHV-;f<i
RAS-3HVRME
RAS-4HVRNE
RA5-5HVRNE
Height (mm)
600
600
800
1240
1240
Width (mm)
792
792
8S0
950
950
Depth (mm)
300
300
31S
31S
315
Weight (kg)
42
42
60
95
97
Airfow Im /mil')
35
35
45
80
90
Sound Pressure (dBA)
46
46
43
45
47
Sound Pressure - Set Back (dBA)
44
44
39
41
43
Liquid - mm (inches)
6,35 (1/4)
6.35 (1/4)
9.S2 (3/8)
9.S2 (3/8)
9.52 (3/8)
Gas ■ mm (inches)
12,70 (1/2)
12.70 (1/2)
1S.88 (S/8)
15.88 (5/8)
15.88(5/8)
Max Pipe Run (rn)
50
50
60
77
77
Max Pipe Lift (m)
30
30
30
30
30
Pre-charged to |m)
30
30
30
30
30
Standing charge (kg)
1.6
1.6
24
3.6
3.6
Refrigerant
R410A
R410A
R410A
R410A
R410A
Phase
Single
Single
Single
Single
Single
Power Supply to
Outdoor '
Outdoor '
Outdoor "
Outdoor '
Outdoor *
Max Current (A)
13
16
21
28
29
fuse Sating (A)
16
20
25
32
32
Interconnecting
LNE + 2*
LNE + 2 *
LNE +2 •
LNE + 2 '
LNE + 2 ■
H-Link Compatible
Yes
Yes
Yes
Yes
Yes
1 Enefirv facts 1
F_CA Approved
Energy Rating (Cool/Heat)
Pending A/A
Pending A/A
Yes A/A
Yes A/A
Yes A/A
EER
3.97
3,28
3.64
3.8S
3.49
COP
4.7S
3.80
415
4.39
4.12
' Note: Power can be supplied either from outdoor unit (via local fused isolator) or separately. Interconnecting wiring should be LNE + 2 core screened comms cable If mains power is to outdoor unit only or 2 core screened comms cable only if power supply is to both indoor and outdoor units.
Operating Conditions
j t U f" 1
U.K. Heat
Mom. i.ooi
Nom. l-u:at
U.K. LOO
Indoor Air Inlet Temperature
DB
27.00
20.00
23,00
22.00
WB
19.00
16.00
Outdoor Air Inlet Temperature
DB
35.00
7.00
30,00
WB
6.00
0,00
WB 6.00 0,00
Piping Length: 7.5 metres; Piping Lift: 0 metres. DB: Dry Bulb; WB: Wet Bulb-Information as advertised in Hitachi Technical Catalogue TCGB0036 rev.l -06/07 or other equivalent source where data was not available. Walter Meier (Climate UK) Ltd cannot be held responsible for any errors in the above information.
Piping Length: 7.5 metres; Piping Lift: 0 metres. DB: Dry Bulb; WB: Wet Bulb.
Information as advertised in Hitachi Technical Catalogue TCGB0036 rev.l - 06/07 or other equivalent source where data was not available. Walter Wleier (Climate UK) Ltd cannot be held responsible for any errors in the above information.
waiter Meier
Walter Meier (Climate UK) Ltd.
Highlands Road, Shirley, Solihull, West Midlands B90 4NL Tel: 0871 663 0664, Fax: 0871 663 1664 uk.climate@waltermeier.com www.waltermeier.com

pageCatalog pdf di En 2012-06-22-01