FUJITSU CASSETTE
CASSETTE
Various remote control options - check model first
Condensate lift pump
Multi-directional airflow
Detachable and washable intake grilles
Ultra quiet
Washable airfilter
■ Quick and easy installation
I Slenderfitfeature
Cooling kW 7.10 to 13.30 Heating kW 7.80 to 16.00
R410A refrigerant
I Indoor Unit Technical Data
AUY24L
AUY30L
AUY36L
AUVA36L
ALIY4SL
AUVA45L
AUY54L
Cooling (kW) - Nominal
7.10
8.50
10.00
10.00
12.50
12.50
13.30
Heating [fcW] • Nominal
7.80
10,00
11.20
11.20
14.00
14.00
16.00
Cooling (kW). UKCondit ion
7.19
9,07
1040
11.84
12.12
13.05
12.SS
Heating fkw} - UK Condition
6.80
9.11
9.55
11.76
11.42
13.56
13.35
Sensible Cooling Duly (UK!
5.96
7.29
8.19
8.19
10.10
9.49
9.93
Sound Pressure Level (dBA)
46/44/39
48/44/41
48/44/41
48/44/41
50/48/45
52/47/47
50/48/45
Height - mm (ex. Grille)
246
296
296
296
296
296
296
Width (mm)
830
830
830
830
B30
830
830
Depth (mm)
830
830
830
830
830
830
830
Weight (kg)
34
37
37
39
40
39
40
Air Flow Eats {m:/h)
1250
1550
1550
16S0
17«)
1750
1700
Model
AOY2JLM
AOV30L
AOY36L
AOYA36L
AOY45L
AOYA45I
AOY54L
Height (mm)
650
830
S30
1290
1290
1290
1290
Width (mm)
830
900
900
900
900
900
900
Depth (mm)
320
330
330
330
330
330
330
Weight (kg)
S 4
62
62
98
105
98
105
Airflow l.ni /hj
3200
3600
3600
6600
6600
6600
6600
Sound Pressure (dBA)
S2
53
54
54
54
55
54
Liquid - mm [inches)
9.52 (3/8)
9,52 (3/8)
9,52 (3/8)
9.S2 (3/8)
9.S2 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas ■ mm (inches)
15.88 (5/8)
15.88 (5/8)
15.83 (5/8)
15.88 (5/8)
15.BS (5/8)
15.88 (5/8)
15.88 (5/8)
Max Pipe Run (m)
25
50
50
50
70
50
70
Max Pipe Lift (m)
15
30
30
30
30
30
30
Pre-charged to(m)
10
15
IS
20
20
20
20
R410A
R41ÛA
R410A
R410A
R410A
Refrigerant
R410A
R41ÛA
Phase
Single
Single
Single
Single
Single
Single
Single
Power Supply to
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Fuse Rating (A)
30
30
30
30
30
30
30
interconnecting
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
E CA Approved
Wo
No
No
Yes
Mo
Yes
No
[ nergy Rating (Cool/Heat)
c/c
C/8
E/C
A/A
m
A/A
E/C
EÉR
2.81
2.97
2.49
3.22
2.81
3.21
2.44
COP
3,25
3,52
3.21
3.71
3.54
3.7]
3.23
Operating Conditions
Nom. Coot
Norn. Heat
U.K. Cool
U.K. Heat
indoor Air Inlet Temperature
DB
27 00
20.00
23.00
23.00
WB
19.00
16.00
Outdoor Air Inlet Temperature
DB
35.00
7.00
moo
1.00
WB
24.00
-1.00
Piping Length: 7.5 metres; Piping Lift: 0 metres. DB: Dry Bulb; W8: Wet Bulb.
Information taken from FC Furofred Limited October 2007 sales literature, data book or other equivalent technical manual where data was not available. UK condition source data can vary therefore some UK duties listed above may differ by a small percentage. Walter Meier (Climate UK) Ltd cannot be held responsible for any errors in the above information.
t Grille supplied with unit. * Hard Wired Remote Control supplied with unit.
waiter Meier
Walter Meier (Climate UK) Ltd.
Highlands Road, Shirley, Solihull, West Midlands B90 4NL Tel: 0871 663 0664, Fax: 0871 663 1664 uk.climate@waltermeier.com www.waltermeier.com

pageCatalog pdf di En 2012-05-22-30