Fujitsu AUY 600mm² Compact Cassette - Walter Meier (Klima International) AG - #1

/ 1


catalogue search
Fujitsu AUY 600mm² Compact Cassette - Walter Meier (Klima International) AG
P. 01
Page:
Fujitsu AUY 600mm² Compact Cassette - Walter Meier (Klima International) AG


See other catalogues for Walter Meier (Klima International) AG

Text version of the page
FUJITSU 600mm1 CASSETTE
■ Condensate lift pump ■ Ultra quiet
■ Multi-directionalairflow * Washableairfilters
■ Compact and quiet ■ Quick and easy installation
■ Motorised louvers Cooiing kW 3.50 to 7.10
Heating kW 4.00 to 8.00
Infra red controller as standard
Optional hard wired control with seven daytime clock
Optional infra red controller
COMPACT CASSETTE
R410A refrigerant
I : u Unit Tei 1 ■ ■ :::.r -
AUY12L
AUYA12L
AUY14L
AUVA14L
AUY18L
AU VAISI
AUVA24L
Cooling (kW) - Nominal
3.50
3.50
4.00
4.30
4.70
5.20
7.10
Heating [fcW] • Nominal
4.00
4.10
4.50
5.00
4.80
6.00
8.00
Cooling (kW) - UKCondit ion
3,77
4,35
4,39
4.98
4.31
5.44
6,99
Heating fkW} - UK Condition
4.48
4.92
4.76
5.87
3.24
6.83
797
Sensible Cooling Duly (UK!
2.59
3.80
2.83
4.32
3.25
3.85
5.20
Sound Pressure Level (dBA)
42/39/36
37/34/31
42/39/36
43/38/34
44/41/38
43/38/34
49/45/40
Height - mm (ex. Grille)
235
245
235
24S
235
245
245
Width-mm (ex.Grille)
580
570
580
570
580
570
570
Depth - mm [ex. Grille)
580+66
570+75
580+66
570+75
580+66
570+75
570+75
Weight (kg)
18
IS
18
15
18
15
17
Air Flow Rate (m'/h)
550
600
SS0
680
620
630
930
I Ouldpor Dull Terlimtal Dalj
Model
AOV12L
AOVA12L
A0Y14L
AOYA14L
AOY18L
AOYA18L
AOYA24L
Height (mm)
650
578
650
578
650
578
578
Width (mm)
830
790
830
790
830
790
790
Depth (mm)
320
300
320
300
320
300
315
Weight (kg)
54
40
54
40
54
40
44
Airflow l.ni /hi
2300
1780
2800
1910
2800
2000
2470
Sound Pressure (dBA)
49
48
49
45
50
50
53
Liquid - mm (inches)
6.35 (1/4)
6,35 (1/4)
6,35 (1/4)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
Gds ■ mm (inches)
9.52 (3/8)
9.52 (3/8)
12.70 (1/2)
12.70(1/2)
12.70(1/2)
12.70(1/2)
15.88 (5/8)
Max Pipe Run (m)
25
25
25
25
25
25
30
Max Pipe Lift (m)
15
15
IS
15
IS
15
20
Pre-charged to (m)
10
15
10
15
10
15
IS
Refrigerant
K41ÜA
R410A
R410A
R410A
R410A
R410A
R410A
Phase
Single
Smgie
Single
Single
Single
Single
Single
Power Supply to
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Fuse Rating (A)
15
15
15
15
20
20
20
interconnecting
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
E CA Approved
Wo
Yes
No
YC-S
Mo
Yes
Yes
E riefgy Eating (Cool/Heat)
8/D
A/A
C/E
A/A
C/D
A/A
A/A
EÉR
3.02
3.33
2.94
3.23
2.85
3.21
3.21
COP
2.86
3,69
2.73
3.73
2.81
3.6.1
3.62
Operating Conditions_Norn. Cool Nom.Heat_U.K. Cool__U.K. Heat
Indoor Air 1:1 let Temperature
DB
27.00
20 00
23.00
22.00
WE
15.00
16.00
Outdoor Air Inlet Temperature
DB
35.00
7.00
30.00
0.00
WB
24.00
-2.00
Piping Length: 7.5 metres; Piping Lift: 0 metres. DB: Dry Bulb; WB; Wet Bulb.
Information taken from FC Eurofred Limited October 2007 sales literature, data book or other equivalent technical manual where data was not available. UK condition source data can vary therefore some UK duties listed above may differ by a small percentage. Walter Merer (Climate UK) Ltd Cannot be held responsible for any errors in the above information.
* Wireless Remote Controller supplied with unit.
waiter Meier
Walter Meier (Climate UK) Ltd.
Highlands Road, Shirley, Solihull, West Midlands B90 4NL Tel: 0871 663 0664, Fax: 0871 663 1664 uk.climate@waltermeier.com www.waltermeier.com

pageCatalog pdf di En 2012-06-22-01