| | | FUJITSU 600mm1 CASSETTE | | |
| | | |
| | | ■ Condensate lift pump ■ Ultra quiet ■ Multi-directionalairflow * Washableairfilters ■ Compact and quiet ■ Quick and easy installation ■ Motorised louvers Cooiing kW 3.50 to 7.10 Heating kW 4.00 to 8.00 | | |
| | | Infra red controller as standard Optional hard wired control with seven daytime clock Optional infra red controller | | |
| | | COMPACT CASSETTE | | |
| | | |
| | | |
| | | |
| | | R410A refrigerant | | |
| | | |
| | | | | | | | | | | | | | | | I : u Unit Tei 1 ■ ■ :::.r - | AUY12L | AUYA12L | AUY14L | AUVA14L | AUY18L | AU VAISI | AUVA24L | | | | Cooling (kW) - Nominal | 3.50 | 3.50 | 4.00 | 4.30 | 4.70 | 5.20 | 7.10 | | | | Heating [fcW] • Nominal | 4.00 | 4.10 | 4.50 | 5.00 | 4.80 | 6.00 | 8.00 | | | | Cooling (kW) - UKCondit ion | 3,77 | 4,35 | 4,39 | 4.98 | 4.31 | 5.44 | 6,99 | | | | Heating fkW} - UK Condition | 4.48 | 4.92 | 4.76 | 5.87 | 3.24 | 6.83 | 797 | | | | Sensible Cooling Duly (UK! | 2.59 | 3.80 | 2.83 | 4.32 | 3.25 | 3.85 | 5.20 | | | | Sound Pressure Level (dBA) | 42/39/36 | 37/34/31 | 42/39/36 | 43/38/34 | 44/41/38 | 43/38/34 | 49/45/40 | | | | Height - mm (ex. Grille) | 235 | 245 | 235 | 24S | 235 | 245 | 245 | | | | Width-mm (ex.Grille) | 580 | 570 | 580 | 570 | 580 | 570 | 570 | | | | Depth - mm [ex. Grille) | 580+66 | 570+75 | 580+66 | 570+75 | 580+66 | 570+75 | 570+75 | | | | Weight (kg) | 18 | IS | 18 | 15 | 18 | 15 | 17 | | | | Air Flow Rate (m'/h) | 550 | 600 | SS0 | 680 | 620 | 630 | 930 | | | | I Ouldpor Dull Terlimtal Dalj | | | | Model | AOV12L | AOVA12L | A0Y14L | AOYA14L | AOY18L | AOYA18L | AOYA24L | | | | Height (mm) | 650 | 578 | 650 | 578 | 650 | 578 | 578 | | | | Width (mm) | 830 | 790 | 830 | 790 | 830 | 790 | 790 | | | | Depth (mm) | 320 | 300 | 320 | 300 | 320 | 300 | 315 | | | | Weight (kg) | 54 | 40 | 54 | 40 | 54 | 40 | 44 | | | | Airflow l.ni /hi | 2300 | 1780 | 2800 | 1910 | 2800 | 2000 | 2470 | | | | Sound Pressure (dBA) | 49 | 48 | 49 | 45 | 50 | 50 | 53 | | | | Liquid - mm (inches) | 6.35 (1/4) | 6,35 (1/4) | 6,35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | 6.35 (1/4) | | | | Gds ■ mm (inches) | 9.52 (3/8) | 9.52 (3/8) | 12.70 (1/2) | 12.70(1/2) | 12.70(1/2) | 12.70(1/2) | 15.88 (5/8) | | | | Max Pipe Run (m) | 25 | 25 | 25 | 25 | 25 | 25 | 30 | | | | Max Pipe Lift (m) | 15 | 15 | IS | 15 | IS | 15 | 20 | | | | Pre-charged to (m) | 10 | 15 | 10 | 15 | 10 | 15 | IS | | | | Refrigerant | K41ÜA | R410A | R410A | R410A | R410A | R410A | R410A | | | | Phase | Single | Smgie | Single | Single | Single | Single | Single | | | | Power Supply to | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor | Outdoor | | | | Fuse Rating (A) | 15 | 15 | 15 | 15 | 20 | 20 | 20 | | | | interconnecting | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E | 3C+E | | | | | | | | E CA Approved | Wo | Yes | No | YC-S | Mo | Yes | Yes | | | | E riefgy Eating (Cool/Heat) | 8/D | A/A | C/E | A/A | C/D | A/A | A/A | | | | EÉR | 3.02 | 3.33 | 2.94 | 3.23 | 2.85 | 3.21 | 3.21 | | | | COP | 2.86 | 3,69 | 2.73 | 3.73 | 2.81 | 3.6.1 | 3.62 | | | | | | | | | | | | | | | |
| | | |
| | | Operating Conditions_Norn. Cool Nom.Heat_U.K. Cool__U.K. Heat | | |
| | | | | | | | | | | | | | Indoor Air 1:1 let Temperature | DB | 27.00 | 20 00 | 23.00 | 22.00 | | | | | WE | 15.00 | | 16.00 | | | | Outdoor Air Inlet Temperature | DB | 35.00 | 7.00 | 30.00 | 0.00 | | | | | WB | 24.00 | | -2.00 | | | | | | | | | | | | | |
| | | |
| | | Piping Length: 7.5 metres; Piping Lift: 0 metres. DB: Dry Bulb; WB; Wet Bulb. Information taken from FC Eurofred Limited October 2007 sales literature, data book or other equivalent technical manual where data was not available. UK condition source data can vary therefore some UK duties listed above may differ by a small percentage. Walter Merer (Climate UK) Ltd Cannot be held responsible for any errors in the above information. * Wireless Remote Controller supplied with unit. | | |
| | | |
| | | waiter Meier | | |
| | | Walter Meier (Climate UK) Ltd. Highlands Road, Shirley, Solihull, West Midlands B90 4NL Tel: 0871 663 0664, Fax: 0871 663 1664 uk.climate@waltermeier.com www.waltermeier.com | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | |