Catalogue Variable Frequency Drive / Inverter - Starvert iH
www.vmc.es
print switch display
Page / 20
Where to buy
this product ?
Request
a Quote
Vector Motor Ibérica - 15006
/ 20
See other catalogues for Vector Motor Ibérica
Text version of the page
Starvert iH
2. Function Group
Code [FUN]
Description of Function Group
Keypad Display
Setting Range
Units
Factory Default
Adjustable during run
45D
Stall Prevention Mode
Stall mode0
None, Acc, Steady, Acc + Steady, Dec, Acc + Dec, Dec + Steady, Acc + Dec+Steady
None
Yes
46D
Stall Prevention Level
Stall levelO
CT: 30 to 150 [%] VT: 30 to 150 [%]
1 1
150 [%] 110 [%]
Yes Yes
47D
Overload Warning Level
OL levelO
CT: 30 to 150 [%] VT: 30 to 110 [%]
1 1
150 [%]
110 [%]
Yes Yes
48
Overload Warning Hold Time
OL time0
1 to 30 [sec]
1
10 [sec]
Yes
49D
Over Current Trip Limit Level
OC lim levelO
CT: 30 to 200 [sec] VT: 30 to 150 [sec]
1 1
160 [%]
110 [%]
Yes Yes
50D
Over Current Limit Time
OC lim. Time0
0 to 60 [sec]
0.1
60 [sec]
Yes
51D
Electronic Thermal Selection
ETH selectO
No, Yes
No
Yes
52D
Electronic Thermal Level
ETH levelO
30 to 150 [%]
1
150 [%]
Yes
53D
Electronic Thermal Characteristic (Motor Type) Selection
Motor type O
General, Special
General
Yes
54D
Number of Motor Poles
Pole number O
2 to 12
1
4
Yes
55D
IPF (Instant Power Failure) Restart Selection
IPF select O
No, Yes
No
Yes
56
Speed Search Acceleration Time
SS acc. time O
0.1 to 600 [sec]
0.1
5 [sec]
Yes
57
Speed Search Deceleration Time
SS dec. TimeO
0.1 to 600 [sec]
0.1
10 [sec]
Yes
58
Speed Search Gain
SS gainO
0 to 200 [%]
1
100 [%]
Yes
59
Restart after Fault Reset Selection
RST-restartO
No, Yes
No
Yes
60
Power-On Start Selection
Power on st O
No,Yes
No
Yes
61
Carrier Frequency
Carrier Freq O
2 to 10 [Hz]
1
6 [Hz]
No
62
PI Control Selection
PI-controlO
No,Yes
No
No
63
PI Proportional Gain
P-gainO
1 to 30000
1
10
Yes
64
PI Integral Gain
I-gainO
1 to 30000
1
50
Yes
65
PI Feedback Selection
PI-fb select O
I, V1, V2
I
No
66
PI Feedback Filter Gain
PI-fb filt.GO
1 to 100 [%]
1
25 [%]
Yes
67
PI Feedback Gain
PI-fb gain O
50 to 250 [%]
0.1
100.0 [%]
Yes
68 69 70
PI Feedback Bias PI Feedback Direction PI I Gain Scale
PI-fb bias
Pl-fb dir O I__term scale O
0 to 200 [%]
Direct,Invert
1 to 100 [%]
0.1 1
100.0 [%] Direct 100 [%]
Yes No Yes
71
PI Controller Error Direction
PI error dir O
Direct,Invert
Direct
No
72
«121
PI Control Bypass
Regul bypassO
No, Yes
No
No
94 1
CT/VT Selection
CT/VT
Constant Trq,Variable Trq
Constant Trq
No
95
Read Parameters into Keypad from Drive
Para. Read O
Q
No, Yes
No
No
96
Write Parameters to Drive from Keypad
Para. WriteO
No,Yes
No
No
97
Initialize Parameters to Factory Default Settings
Para. InitO
Q
No,Yes
No
No
98
Parameter Write Protection
Para. Lock
0 to 255
1
0
Yes
*9)
Default value depends on the drive capacity,
-10)
FUN 41 is set at its drive capacity before shipping outside. However, drive loses its capacity information after parameter initialization in FUN 97, If the parameters are initialized, be sure to re-set the drive capacity to the right capacity,
Carrier Frequency according to the drive Capacity (The Carrier Frequency is set to 3kHz for VT Rating)
type
SettingRange
Factory Default
type
SettingRange
Factory Default
SV030ÌH-2
2 to 10
6kHz
SV075ÌH-4
2 to 7
6kHz
SV037ÌH-2
2 to 10
6kHz
SV090ÌH-4
2 to 6
6kHz
SV045ÌH-2
2 to 8
6kHz
SV110ÌH-4
2 to 6
6kHz
SV055ÌH-2
2 to 8
6kHz
SV132ÌH-4
2 to 5
5kHz
SV030ÌH-4
2 to 10
6kHz
SV160ÌH-4
2 to 4
4kHz
SV037ÌH-4
2 to 10
6kHz
SV220iH-4
2 to 4
4kHz
SV045ÌH-4
2 to 8
6kHz
SV315ÌH-4
2 to 4
4kHz
SV055ÌH-4
2 to 8
6kHz
SV375ÌH-4
2 to 4
4kHz
*12)
VT is available only for 440V class industrial inverter.
73
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
pdf-page pdf di En 2008-12-49-03