Text version of the page
1912
INSULATED CONDUCTORS U 35
Conductor code: U= unipole insulated conductor
35= shroud size
200, 230, 300, 400, 450, 500= conductor cross sectional area (mm U 35 C >
2 )C= copper conductor
AE= Aluminium conductorcontact surface stainless steel Length: 6.25 m is standard length;
other lengths are available Support spacing: – for straight runs and vertical inside and outside curves:2500 mm– for horizontal curves up toR >
RH = Radius Horizontal curve 41 H = 15 m >
(1) :1250 mm– for horizontal curves overR >
H = 15 m:2500 mm >
33 Conductor spacing: U 35 AE – 90 mm for collectors UST200/35, UDST 400/35 and feed UE– 130 mm for collectors UST 300/35, UDST 600/35 and feed UEG >
23,5 47 Curves: >
23,5 factory prepared Heating system: availableSee page 4 for shroud properties. >
9 (1) Recommendation Type U 35/200 CU 35/300 CU 35/400 CU 35/500 CU 35/230 AEU 35/450 AE Weight (kg/m)2.4003.4004.3006.1001.0701.650 Standard shroud, color green Cat.-No. phase >
(2) 175 20 •175 21 •175 22 •175 33 •175 41•175 45•Cat.-No. ground >
(2) 175 26 •175 27 •175 28 •175 34 •175 42•175 46• High temperature shroud, color gray Cat.-No. phase >
(2) 175 23 •175 24 •175 25 •175 35 •175 43•175 47• Cat.-No. ground >
(2) 175 29 •175 30 •175 31 •175 36 •175 44•175 48• >
Engineering Data
Leakage Distance ofcovers mmmaxvoltageVContinuousAmp. capacityA/35 °CResistanceOhm/1000 mImpedance (3) Ohm/1000 mon 50 Hz, conductor spacing90 mm 130 mm TypeCross sectional area copper mm 2 U 35/200 C 2008510006000.0940.1560.174 U 35/300 C 3008510007200.0600.1380.159 U 35/400 C 4008510008600.0460.1320.154 U 35/500 C 50085100012500.0340.1310.152 U 35/230 AE >
(4) 2308510005000.1340.1830.199 U 35/450 AE >
(4) 4508510008000.0690.1430.163 >
Bolted joint splices
60 TypeWeight kgCat.-No. UV 35/200-300 0.882175 012 >
77124 UV 35/400 1.021175 126 UV 35/500 1.273175 369 UV 35/200-300 K 4 >
(5) 0.882175 013 >
260 M 10 UV 35/400 K 4 >
(5) 1.021175 127 UV 35/500 K 4 >
(5) 1.273175 370 UV 35/230 AE 0.674175 491 UV 35/450 AE 0.776175 492 UV 35/230 AE K 4 >
(5) 0.674175 495 >
88 88 UV 35/450 AE K 4 >
(5) 0.776175 496 >
34
(2) Add last number (1, 2, 3, 4, 5 or 6 m length suffix) in accordance to bars required, whereby last number 6 relates to the standard 6.25 m sections. (3) Based on 50 Hz. (4) The collector of the AE-conductor which are working with only ≤10 m/min. travel speed or stand most of the time are only permitted to work with 50 % of the continuous current. (5) Stainless steel hardware