Vacon NXS - 12 Pages

VPCON NXS STPNDPRD I/O
OPT-A1
OPT-A2
Terminal Defaults settings
Programmable
+24 V GND
Terminal
Defaults settings
Programmable
> 1
+10V AI1 + AI1-
Reference voltage Frequency reference 0-10 V AI common [GND]
21 R01
22 R01
23 R01
-10- + 10 V, 0/4-20 mA Differential
RUN
Many possibilities
1...10 kfi
0-20mA, 0/-10 V-10 V
GND
AI2+ AI2-
Frequency reference 4-20 mA AI common [differential]
24 R02
230 VAC 25 R02
FAULT Many possibilities
Control supply [bidirectional]
I/O Ground
Start forward
Start reverse
External fault input
Common for DIN1 - DIN3 [GND]
6 7 8 9
10 11
+24V GND DIN1 DIN2 DIN3 CMA
Many possibilities Many possibilities Many possibilities Floating
OPT-A3 (alternative)
Control supply [bidirectional]
I/O Ground
Multi-step speed select 1 Multi-step speed select 2 Fault reset
Common for DIN4 - DIN6 [GND]
12 13 14 15 16
17 18
19
+24V
GND DIN4 DIN5 DIN6
CMB
Terminal
Defaults settings
Programmable
21 R01
22 R01
/
RUN
Many possibilities
23 R01
i
25 R02
FAULT
Many possibilities
26 R02
i
28 TI1 +
Thermistor
Warning,
29 TI1-
input fault
no response
+24 V GND
Many possibilities Many possibilities Many possibilities Floating
-0"
230 VAC
Output frequency [0-20 mA]
AO common [GND]
AO1 + Ad-
Many possibilities
4-20 mA, 0-10 V
PTC
■do-
20 DO1
Many possibilities
READY, I < 50 mA, U < 48 VDC
Default settings of OPT-A1, OPT-A2 and OPT-A3 for the Basic and Standard Applications.
OPTION
ORDERTYPECODE
AVAILABILITY
NOTE
IP54 enclosure
Factory option
All
Replace '2' by '5' in the type code, e.g. NXS02605A5H0 (SSS...]
IP5-FR_
FR4, FR5, FR6
IP54 kit, e.g. IP5-FR4
Through hole mounting
Factory option
All
E.g. NXS02605ATH0STS..., IP54 back, IP21 front, kits available
Integrated brake choppers
Standard
FR4-6/230, 500 V
E.g. NXS00455A2H1 (SSS...]
Factory option
FR7-, FR6-/690 V
E.g. NXS02605A2H1 (SSS...]
External brake resistors (380 - 500 V range]
BRE-0022-LD-5
00035-00225
LD = Light duty: 5 sec nominal torque braking from
nominal speed decreasing linearily to zero, once per 120 sec.
HD = Heavy duty: 3 sec nominal torque braking at
nominal speed + 7 sec nominal torque braking from nominal
speed decreasing linearily to zero, once per 120 sec.
Replace LD by HD in the type code, e.g. BRE-0105-HD-5
Brake resistors are also available for 208-240 V and 525-690 V NXS drives
The brake resistor manual is available for more precise selection
Overtemp. protection thermistor included in HD types
BRE-0031-LD-5
00315
BRE-0045-LD-5
00385-00455
BRE-0061-LD-5
00615
BRE-0105-LD-5
00725-01055
BRE-0300-LD-5
01405-03005
Integrated brake resistors
Factory option
FR4-6/500 V
Replace '1' by '2' in the typecode, e.g. NXS00455A2H2 (SSS...]
Light duty: 2 sec nominal torque braking from
nominal speed decreasing linearily to zero, once per 60 sec.
Graphical display panel
Factory option
All
Replace 'A' by 'G', e.g. NXS00455G2H1 (SSS..], supports Chinese & Russian
PAN-G
All
Order typecode when ordered separately
Panel door installation sets
DRA-02B [-04B, -15B]
All
Length of RS232C cable is specified in the typecode, e.g. DRA-02B includes 2-meter RS232C cable
Varnished circuit boards
Factory option
All
Frame sizes FR4-FR8: replace the 'S' by 'V', e.g. NXS00455A2H1SSV..., frame size FR9: replace 'S' by 'G'
C-level RFI-filters
Factory option
FR4-6/500 V
Replace 'H' by 'C' in the typecode, e.g. NXS00455A5C1 (SSS..]
Du/dt & sinus filters
Available for all drives, contact local Vacon supplier
7
Vacon NXS
  1. P. 1

  2. P. 2

    RELIABLE CHOICE The Vacon NXS is a compact AC drive in the power range of 0.37-200 kW and supply voltages of 208—690 V for heavy use in...
  3. P. 3

    DESIGN & DIMENSIONS The mechanical design is extremely compact. The IP54 units in particular are the smallest AC drives on the market. All...
  4. P. 4

    PRODUCT RANGE Mains voltage 208—240 V, 50/60 Hz, 3 Loadability Motor shaft power Low High 230 V supply AC...
  5. P. 5

    PRODUCT RPNGE Mains voltage 525—690 V, 50/60 Hz, 3 Loadability Motor shaft power Low High 690 V supply ...
  6. P. 6

    VflCON NXS CONTROL UNIT
  7. P. 7

  8. P. 8

    first-class usability The uncluttered text display panel with a well-defi ned menu structure and functions such as parameter copy and start-up wizard...
  9. P. 9

    SOFTWPRE MODULPRITY Multipurpose Basic Pump and Fan Control The AU-in-One application package has seven applications (=default...
  10. P. 10

    emc and installation environment 3 2 1 2 4 5 > 2ND ENVIRONMENT1ST ENVIRONMENT The product family standard EN61800-3 sets limits for both emissions...
  11. P. 11

    TECHNICPL DPTP Mains Input voltage Um 208...240 V; 380...500 V; 525...690 V; -10%...+10% connection Input frequency 45...66 Hz ...
  12. P. 12

    Vacon Plc Runsorintie 7, 65380 Vaasa, FinlandTel. +358 (0)201 2121, Fax +358 (0)201 212 205www.vacon.com, Email: info@vacon.com Vacon Partner >BC00146A...
Text version

All VACON catalogues and technical brochures

  1. VACON X-series

    8 Pages

    En
  2. VACON 100

    12 Pages

    En
  3. Vacon NXP and NXC

    13 Pages

    En
  4. Vacon 8000 WIND

    8 Pages

    En
  5. Vacon 100 HVAC

    8 Pages

    En

Archived catalogues

  1. Vacon NXL

    4 Pages

    En