You may also be interested in
Sensor, Temperature probe, Capacitive sensor, Probe, Temperature sensor
Text version of the page
UPSI ZI des Grands Godets –
Courriel : contact@upsi.fr
951 Rue Marcel Paul – 94500 CHAMPIGNY/MARNE–FRANCE www.upsi.fr -Tél : +33 1.45.16.18.20 – Fax : +33 1.45.16.18.29
UMIDITY TEMPERATURE
4 x 2 wires 4-20 mA
Twin probes
Single Supply 7 to 40 V DC with no influence on Accuracy
Line resistor max 1500 Ohms at 40V
Accuracy ± 3% RH ± 0.5° C
Galvanic insulation between all Channels
Connection screw terminals for Wires 0.2 to 2.5 mm˛ ( 26 to 14 AWG)
Rail DIN
CONNECTIONS
MECHANICAL
Dimensions (mm)
Channels
Measurement
Operating Range
Accuracy
Output
Probe N°1
Relative Humidity
0 to 100 %RH
±3%RH Full Range
4 to 20 mA
Temperature
0 to 100 °C
±0.5°C
4 to 20 mA
Probe N°2
Relative Humidity
0 to 100 %RH
±3%RH Full Range
4 to 20 mA
Temperature C
0 to 100 °C
±0.5°C
4 to 20 mA
SSuppllyy
TTemperratturreCCHH11
HHumiiddiittyyCCHH11
HHumiiddiittyyCCHH22
TTemperratturreCCHH22
This leading system has been designed for industrial drying and is very popular notably in the tobacco drying field, due to its accuracy and high resistance. This system is made up of two small probes in stainless steel provided with special anti-chemicals (2 M) filters. This system measures humidity and temperature at the entry and exit point, enabling automation control optimization, moreover it is quick to fix onto DIN rail installations.
|
|