| | | Call U.S.: (954) 346-2442 • sales@unipower-corp.com Call U.K.: +44(0) 1903 768200 • info@unipower-europe.com | | |
| | | |
| | | SPECIFICATIONS, TSGR1U4 RACKS/SHELVES, 19-INCH | | |
| | | |
| | | FRONT VIEW | | |
| | | |
| | | A | | B | | C | | D | | |
| | | |
| | | SINGLE BUS DC OUT DUAL A/B AC IN | | 4-C14 AC INLETS | | |
| | | DC OUT | | |
| | | TSGR1U4A BACK VIEW | | |
| | | J1 | | |
| | | |
| | | |
| | | I® © | | |
| | | |
| | | |
| | | |
| | | |
| | | 2-C20 AC INLETS | | |
| | | SINGLE BUS DC OUT DUAL A/B AC IN DUAL A/B BUS DC OUT DUAL A/B AC IN | | |
| | | © © | | |
| | | | | |
| | | DC | | TSGR1U4B
| |
| | | J1 | | |
| | | |
| | | |
| | | |
| | | |
| | | 0UT BACK VIEW | |
| | | © © | | |
| | | |
| | | |
| | | C&D | | |
| | | A&B | | |
| | | |
| | | |
| | | 2-C20 AC INLETS | | |
| | | TSGR1U4C BACK VIEW | | |
| | | DC OUT (A&B) | | |
| | | DC 1 OUT -[ C&D (C&D) 1 | | J1 | | |
| | | J2 | | |
| | | |
| | | |
| | | |
| | | |
| | | A&B | | |
| | | |
| | | |
| | | |
| | | |
| | | RACK/SHELF DEPTH IS 13.88 INCHES (353 MM). THERE ARE PLASTIC SAFETY COVERS OVER THE DC OUTPUT BUS BARS. | | |
| | | |
| | | MAXIMUM RATED OUTPUT FOR 4 MODULES | | |
| | | SINGLE DC OUTPUT BUS J1 | | |
| | | |
| | | | | | | | | | | MODULES | NON-REDUNDANT | 3+1 REDUNDANT | | | | RSG3000 RSG5000 RSG7000 | 13.6VDC @ 132.0A 1800W 27.2VDC @ 73.6A 2000W 54.4VDC @ 40.4A 2200W | 13.6VDC @ 99.0A 1350W 27.2VDC @ 55.2A 1500W 54.4VDC @ 30.3A 1650W | | | | TSG3000 TSG5000 TSG7000 | 12.0VDC @ 150.0A 1800W 24.0VDC @ 83.2A 2000W 48.0VDC @ 46.0A 2200W | 12.0VDC @ 112.5A 1350W 24.0VDC @ 62.4A 1500W 48.0VDC @ 34.5A 1650W | | | | TSF3000 TSF5000 TSF7000 | 12.0VDC @ 100.0A 1200W 24.0VDC @ 58.4A 1400W 48.0VDC @ 33.2A 1600W | 12.0VDC @ 75.0A 900W 24.0VDC @ 43.8A 1050W 48.0VDC @ 24.9A 1200W | | | | | | | | | | |
| | | 13 | | |
| | | |
| | | |
| | | Standard 25-Pin Subminiature D Connector | | |
| | | |
| | | 25 | | |
| | | |
| | | | | | | | | | | | | | J1 SIGNAL CONNECTOR | | | | PIN | FUNCTION | PIN | FUNCTION | | | | 1 | Inhibit | J | 4 | AC Power Fail - A | | | | 2 | N.C. | | 5 | DC Power Good - A | | | | 3 | Overtemp. Warn. - A | _ | 6 | AC Power Fail - B | | | | 4 | Overtemp. Warn. - B | _ | 7 | DC Power Good - B | | | | 5 | Overtemp. Warn. - C | _ | 8 | AC Power Fail - C | | | | 6 | Overtemp. Warn. - D | _ 1 | 9 | DC Power Good - C | | | | 7 | V Adjust - D | 20 | AC Power Fail - D | | | | 8 | +5V Standby | 21 | DC Power Good - D | | | | 9 | SDA | 22 | -Sense | | | | J | 0 | Current Share | 23 | -Sense | | | | | 1 | +Sense | 24 | V Adjust - A | | | | | 2 | V Adjust - B | 25 | V Adjust - C | | | | 1 | 3 | SCL | | | | | | | | | | | | | | | |
| | | |
| | | | | | | | | | | | | AC LINE CORDS: Order by Part No. | | | | V/A | TSGR1U4 | NEMA | LENGTH | PART NO. | | | | | SUFFIX | PLUG | FT/M | | | | | 125/15 | A | 5-15 | 6/1.83 | 364-1412-0000 | | | | 125/20 | B, C | 5-20 | 8/2.44 | 364-1416-0000 | | | | 250/15 | A | 6-15 | 6/1.83 | 364-1414-0000 | | | | 250/20 | B, C | 6-20 | 8/2.44 | 364-1413-0000 | | | | | | | | | | | | |
| | | |
| | | |
| | | DUAL DC OUTPUT BUSES J1orJ2 , | | |
| | | NOTES: | | |
| | | |
| | | 13 | | | All connections are made to the rear of the rack/shelf. The TSGR1U4A has one C14 AC inlet per module. The "B" and "C" rack versions have one C20 AC inlet per two modules. | | |
| | | 1. | | |
| | | |
| | | |
| | | Standard 25-Pin Subminiature D Connector | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | PIN | FUNCTION | PIN | FUNCTION | | | | 1 | Inhibit | J | 4 | AC Power Fail - A or C | | | | 2 | N.C. | | 5 | DC Power Good - A or C | | | | 3 | Overtemp. Warn.- A or C | _ | 6 | AC Power Fail - B or D | | | | 4 | Overtemp. Warn.- B or D | _ 1 | 7 | DC Power Good - B or D | | | | 5 | — | 18 | — | | | | 6 | — | 19 | — | | | | 7 | — | 20 | — | | | | 8 | +5V Standby | 21 | — | | | | 9 | SDA | 22 | -Sense | | | | J | 0 | Current Share | 23 | -Sense | | | | | 1 | +Sense | 24 | V Adjust - A or C | | | | — | 2 | V Adjust - B or D | 25 | — | | | | 1 | 3 | SCL | | | | | | | | | | | | | | | |
| | | 2. Standby return is connected to -Sense lead. Current rating of +5V standby is 100mA. All signals are referenced to -Sense lead. 3. Module A is on the left and module D on the right, as seen from the front of the rack/shelf. From the rear, the rightmost AC inlet(s) go to modules A & B as shown. 4. For rack/shelf "A" and "B" versions, all four module DC outputs are connected in parallel. For the "C" version, module A and B outputs are paralleled and module C and D outputs are paralleled. Module A & B signals go to J1; module C & D signals go to J2. 5. All racks/shelves come with universal mounting brackets for 19- or 23-inch rack mounting. 6. For details on the I2C function (option Z), contact the factory. I2C signals are on J1 & J2 pins 9 & 13. | | |
| | | |
| | | |
| | | Sigma-RSG-TSG revD-10-12-05 | | |
| | | www.unipowercorp.com | | |
| | | |
| | | |
| | | Copyright © 2005 Unipower Corporation. All rights reserved. | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |