Flange and Bolting Data –
Figures 810, 813, and 815
ASME CLASS 125/150
Size Diameter of No. of Bolt
(in.) Bolt Circle Bolts Thread
2 43/4 4 5/8 - 11
21/2 51/2 4 5/8 - 11
3 6 4 5/8 - 11
4 71/2 8 5/8 - 11
5 81/2 8 3/4 - 10
6 91/2 8 3/4 - 10
8 113/4 8 3/4 - 10
10 141/4 12 7/8 - 9
12 17 12 7/8 - 9
14 183/4 12 1 - 8
16 211/4 16 1 - 8
18 223/4 16 13/4 - 7
20 25 20 13/4 - 7
24 291/2 20 11/4 - 7
301 36 28 11/4 - 7
361 423/4 32 11/2 - 6
Note
1. ASME Class 125 Only
Flange and Bolting Data – Figure 809
ASME CLASS 300
Size Diameter of No. of Bolt
(in.) Bolt Circle Bolts Thread
2 5 8 5/8 - 11
3 65/8 8 3/4 - 10
4 77/8 8 3/4 - 10
5 91/4 8 3/4 - 10
6 105/8 12 3/4 - 10
8 13 12 7/8 - 9
10 15 16 1 - 8
12 18 16 11/8 - 7
Recommendations for Installation Position
1. Position the check valve to promote smooth flow.
2. Allow clearance for disc movement.
3. Install the valve in horizontal or upward flow for proper valve closure.
Caution Do not use with reciprocating compressors, or in other pulsating services.