( in force since January 1st 1996) classificazione classificazione secondole vecchie norme CEI EN50086 The general standard EN50086.1 is divided in four subnorms which prescri-be specifical tests to be effected on each product: EN 50086-2-1for rigid conduitEN 50086-2-2for pliable conduit (corrugated)
EN50086-2-3for flexible conduit (sheaths)
EN 50086-2-4for underground pipes >
prodotto TF1 >
(PVC corrugated - black and coloured 3 - 3 - 2 -1 P=heavy >
(750 Newton) RF15 >
(PVC rigid - gray) 3 - 3 - 2 -1 P=heavy >
(750 Newton) RF20 >
(PVC rigid - gray) 4 - 3 - 2 -1 not appliable ICTA >
(PP corrugated - gray) 3 - 4 - 2 -2 ICT 390 TCT >
(PP corrugated - orange) 2 - 2 - 2 - 2 TCT 90L TFG >
(spiral sheaths) 2 - 3 - 1 -1 not appliable CAF >
(underground pipes) 3 - 3 - 2 -2 not appliable >
UNDERGROUND AND PLASTIC FITTINGSSYSTEMS FLEXIBLE PLIABLE AND PLAIN SELF-RECOVERING CONDUITS AND FITTING SYSTEMS
FIELD OF APPLICATION FIELD OF APPLICATION >
Underground conduit systems and metallic and non-metallic conduit fittings, assem-bled, threaded and non. Conduit systems and fittingsConduit systems and pliable metallic fittings and non, assembled, threaded and non MARKINGS CLASSIFICATIONS >
Heavy-duty conduit: Trade mark; Product identification mark; L (light); N (normal)
Markings: between 1 and 3m
Fittings: Trade mark; Product identification mark; L; N Composed of 12 figures MARKINGS AND DOCUMENTATION >
Conduit: Trade mark; Product identification
Conduit may be also marked with classification code of at least 4 figures.
Conduit markings: Spacing pref. at intervals of 1m but not greater than 3m;
each spacing marked at least once
Fittings: Code of at least 4 figs; or labelling on product or packaging
Manufacturer must specify min. inner diameter of system DIMENSIONS >
Table 101 only conduits (lowest min. ø)
Sizes: 25; 32; 40; 50; 63; 75; 90; 110; 125; 140; 160; 180; 200; 225; 250mm MECHANICAL PROPERTIES >
Bending test: 3 tests: room temp. -3 tests: -5°C
Pulley radius: 15 x outer ø
Conduit should not flatten; Verify by gauge 95% min inner ø
Impact resistance:
Speed 15mm/min.; value force which causes flattening 5% inner diameter
prev. calculated. When flattening reaches 5%, applied force should be at least
450N L: 200mm
Low temp. resistance test:
Not applicable
Light heavy-duty conduit: 3kg; Height H depends on diameter (100÷500mm)
Normal heavy-duty conduit: 5kg; Height H depends on diameter (300÷800mm) DIMENSIONS >
Outer diameters: EN 60423 (as per standards)
Inner diameter: min. diameter of system as specified by manufacturer SIZES >
(in mm)6; 8; 10; 12; 16; 20; 25; 32; 40; 50; 63; 75mm. MECHANICAL PROPERTIES >
Non-metallic bending test: all diameters
Plain conduits: 30 x outer ø
Corrugated conduits: 12 x outer ø bending test fig. 101
Verify using gauges 80% inner ø (Supplied by manufacturer) fig. 102
Compression test:
Light 320N; Medium 750N; Heavy 1250N; Ex heavy 4000N
Flattening: 25÷50% self-recovering
Low temp. resistance test:
Not applicable
Light: 1kg H=100mm
Medium: 2kg H=100mm
Heavy: 2kg H=300mm
Ex heavy: 6,8kg H=300mm
Tensile test: Conduit + fittings
Suspended load test: Fittings FLAME PROPAGATION RESISTANCE >
Conduits: Lenght 675mm
Bunsen burner as IEC 695-2-4 1KWSteel conduit in test
Time of exposure to flame: depends on conduit thickness
Fittings: Glow wire 750°C DIELECTRIC STRENGTH >
Water temp.: 23 ±2°C
Salt water (lg/l)
Insulation: water temp.: 23 ±2°C
Fittings: According to manufacturer’s instructions With the receipt of New Approach Directives, the products which apply within their fieldof application must be manufactured in conformity with the relevant and essential requi-
rements that must be met to be put in the market and in service across the European
Community.A presumption of conformity to European New Approach Directives is the affixing of theCE Marking on the product and/or on its instruction manual and/or on the packaging.The Directives that can be applied to TUBIFOR products are the following: Dir. 72/23/CEEreceipt with the Rule Nr. 791 dtd. 18/10/1977 and amended by the Dir. 93/68/CEE related
to the relevant safety standards of electrical material included in the Low Voltage Directive.The CE Marking must be applied since01/01/1996 according to Dir. EMC (89/399/CEE and 93/68/CEE);01/01/1997 according to Dir. LVD (73/23/CEE and 93/68/CEE);TUBIFOR products which apply to Directives bear the CE Marking since the above indica-ted dates. FLAME PROPAGATION RESISTANCE >
Conduits: length 675mm
Bunsen burner as IEC 695-2-4 1 KW
Time of exposure to flame: depends on conduit thickness
Verification: tissue paper burning test plus other verifications
Fittings: Glow wire 750°C HEAT RESISTANCE >
Heat compression test: Temp. as
per classification plus weight
External influences: Verify protection grade IP 6