You may also be interested in
Air filter, Smoke detector, Ventilation diffuser, Ventilation grill, Blow-off nozzle
Text version of the page
To change without notice · All rights reserved © TROX GmbH (6/2006)
Testing · Specification Text
TROX Minipleat Filter Panels F757 and
F759 consisting of:
Fibre board or particle board casing;
Filter media of high grade moisture resistant
glass fibre paper with textile spacer.
The Minipleat Filter Panels are packed in
damage-resistant cartons for transportation.
TROX Minipleat Filter Panels F780 and F781
consisting of
Casing of fibreboard, galvanized sheet steel,
stainless sheet steel or aluminium extrusion;
Filter media of high quality moisture resistant
glass fibre paper with thermoplastic adhesive
spacer.
Minipleat filter panel F781 is type tested for
leaks by oil-mist test at factory.
Minipleat filter panels F780 and F781 are
packed in damage-resistant cartons for
transportation.
Technical data:
Filter class to EN 779 _________________________
Average Efficiency ____________________________ %
Filter class to EN 1822 ________________________
Extraction efficiency to EN 1822 _______________ %
Dimensions (B x H x T) _______________________ mm
Nominal volume flow _________________________ l/s (m3/h)
Initial pressure differential _____________________ Pa
Max. operating temperature ___________________ °C
Max. relative humidity ________________________ %
Net weight __________________________________ kg
Order number _______________________________
Manufacture: TROX
Specification Text
Item No. Specification
Price / Each
9
Testing of particulate filters
EN 779: Particulate air filters for general room
air-conditioning
This Norm is concerned with the performance testing of
particulate air filters with an Efficiency against atmospheric
dust of up to 98% (see leaflet: F0/2/EN/.) The particulate
filters are divided into filter grades F5 to F9 according to
their test results to EN779.
Testing of high efficiency particulate filters
EN 1822: High efficiency particulate filters
(HEPA and ULPA)
This new European Norm testing procedure is based on
particle counting using a liquid test aerosol of varying
particle sizes.
The filters are rated by filter class according to extract
efficiency or penetration.
Leak test
Tests are carried out in accordance with an oil mist test
to EN 1822, a local scan test to verify the filters are free
from leaks.
TROX offers the following:
F781: Filter panels individually tested for leaks
0 = Standard with oil mist test
or at increased price:
E = Scan test (particle counting)
|
|