catalogue search
|
You may also be interested in
LED lighting, Manual call point, Alarm siren, Loud-speaker, High power LED
Text version of the page
490s-t strobe
3" dia.
5“
1/2” Pipe Mount
NFPA Definitions
Class I, Division 2.
A location (1) in which volatile flammable liquids or flammable gases are handled, processed or used, but in which the liquids, vapors or
gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or
breakdown of such containers or systems, or in case of abnormal operation of equipment; or (2) in which ignitable concentrations of gases or
vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through failure or abnormal operation
of the ventilating equipment; or (3) that is adjacent to a Class I Division 1 location, and to which ignitable concentrations of gases or vapors
might occasionally be communicated unless such communication is prevented by adequate positive–pressure ventilation from a source of
clean air and effective safeguards against ventilation failure are provided. [See Section 500–4(b) of NFPA 70, National Electrical Code.]
Class II, Division 2.
A location in which (1) combustible dust will not normally be in suspension in the air in quantities sufficient to produce explosive or ignitable
mixtures and dust accumulations are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus; or
(2) dust may be in suspension in the air as a result of infrequent malfunctioning of handling or processing equipment and dust accumulations
resulting therefrom may be ignitable by abnormal operation or failure of electrical equipment or other apparatus.
[See Section 500–5 (b) of NFPA 70, National Electrical Code.]
Specifications
Item
Description
Lamp Type
5001 Xenon strobe lamp
Lens Type
470S–L–Color ( please specify lens color )
Voltage and Amperage
12–80VDC draws 0.4A average @ 12VDC draws tapering to
0.05A average @ 80VDC
16–24VAC draws 0.35A average
120VAC draws 0.04A average
Temperature Code
Class I T2C 230º C
Do not install where the operating temperature exceeds the
ignition temperature of the hazardous atmosphere.
Temperature Rating
–40º C to +65º C
Power Supply
Output 2.7 Watts (
single flash )
2.3 joules per flash
Flash Rate
Architect and Engineer Specifications
Hazardous Location visual signaling beacon shall be Tomar
model number series 490S-1280T, 490S-120T or approved
equal. The beacon shall be UL Listed Class I, Division II,
Groups A,B,C, and D; Class II, Division II, Groups F and
G; and Class III for use in specified hazardous locations as
classified by the National Electric Code. The light source
shall be a plug-in field replaceable single-flash xenon strobe
lamp. The warning signal must have built-in RFI filters to
protect against radio interference and spike voltages. It
shall be polarity protected, and have a power supply fully
potted in polyurethane. Voltage ranges shall be 12-80VDC
or 120 VAC. The warning light shall be rated NEMA 4X and
have a screw-on Lexan® lens.
60 to 80 flashes per minute
Size and Weight
5” tall x 3” dia. x 0.6 lbs
Encapsulation
Fully potted in urethane material with no exposure to
High Voltage possible
( 127mm x 76mm x 0.27kg )
41
|