| | | Improved Performance - Less Maintenance | | |
| | | |
| | | Easy Maintenance All internal parts can be accessed by removing the trap cover. | | |
| | | Overexpansion Protection | | |
| | | |
| | | The thermo-element is protected from overexpansion by the overexpansion spring, providing stable performance and long life. | | |
| | | |
| | | |
| | | Labor-Saving Design | | |
| | | Durable Construction | | |
| | | |
| | | |
| | | A unique nipple is incorporated into the trap inlet to facilitate installation and removal of the trap with wrenches and channel-locks. | | |
| | | No leakage through the trap orifice, due to the durability and smooth sealing of the ball valve. | | |
| | | |
| | | Improved Valve Seat | | |
| | | |
| | | A larger valve orifice permits more rapid purging of rust, scale and initial air, allowing faster warm-ups. | | |
| | | |
| | | Radiator Trap | | |
| | | RI3A | | |
| | | |
| | | |
| | | |
| | | Cold 185 | | |
| | | water F Hot water | | |
| | | 5000 | | |
| | | | | | | | | | | Body Material | Brass | | | | Connection | Screwed | | | | Size | V2", 3/4M | | | | Max. Operating Pressure | PMO | 45 psig | | | | Min. Operating Pressure | 1.5 psig | | | | Max. Operating Temperature | TMO | 292 °F | | | | Max. Allowable Pressure | PMA | 45 psig | | | | Max. Allowable Temperature | TMA | 292 F | | | | Open-Close Temperature | approx. 203 °F - 212 °F | | | | | | | | | | |
| | | |
| | | 3000 2000 1000 700 500 300 | | |
| | | it '5 a Ol im u vi ˇ5 | | |
| | | |
| | | 200 | | |
| | | |
| | | |
| | | 0.1 0.3 0.5 1 2 3 5 10 2030 45 Differential Pressure (psi) | | |
| | | |
| | | To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside the specification range. Local regulations may restrict this product below the conditions quoted. | | |
| | | |
| | | CAUTION | | |
| | | |
| | | ■ | | Operation | | |
| | | |
| | | |
| | | |
| | | 0 | | |
| | | |
| | | At low temperatures during start-up, the thermo-element (A) is fully retracted, keeping the valve fully open and allowing air and condensate to be discharged. | | After discharging the initial condensate from start-up, as the condensate temperature raises past approx. 212 °F the thermo-element (A) expands and pushes the valve shut. | | When the temperature of the condensate in the trap drops below approx. 203 °F, the thermo-element (A) retracts, discharging condensate. If the temperature raises above approx. 212 °F, the valve shuts again as in step 2. | | |
| | | |
| | | |
| | | |
| | | DO NOT DISASSEMBLE OR REMOVE THIS PRODUCT WHILE IT IS UNDER PRESSURE. Allow Internal pressure of this product to equal atmospheric pressure and Its surface to cool to room temperature before disassembling or removing. Failure to do so could cause burns or other injury. READ INSTRUCTION MANUAL CAREFULLY. | | |
| | | | | |
| | | CAUTION | | |
| | | | |
| | | |
| | | |
| | | TLV CORPORATION 13901 South Lakes Drive, Charlotte, NC 28273-6790 Phone: 704-597-9070 Fax: 704-583-1610 Member of E-mail: tlv@tlvengineering.com M^cs | | |
| | | ISO 9001/ISO 14001 | | |
| | | Manufacturer | | |
| | | |
| | | |
| | | | | |
| | T | f® co., ltd. Kakogawa, Japan is approved by LRQA Ltd. to ISO 9001/14001 | | |
| | | |
| | | |
| | | |
| | | | FLUID CONTROLS INSTrTUTE | | |
| | | For Technical Service 1-800 '' TLV TRAP" | |
| | | |
| | | Internet World Wide Web URL http://www.tlv.com Pamphlet A2008-2 Rev. 1/2008 Specifications subject to change without notice. | | |
| | | (M) | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |