MICROPROCESSOR-BASED RELAY FOR OVERCURRENT AND EARTH FAULT PROTECTION WITH DIRECTIONAL FUNCTIONS OF OVERCURRENT AND EARTH FAULT PHASE & RESIDUAL OVERCURRENT, PHASE & AND GROUND DIRECTIONAL, UNDER/OVERVOLTAGE PROTECTIVE RELAY

General

The relay type SSG is intended for the protection against over- loads, short circuits and earth faults in radial network, ring mains or variable structure networks, whatever neutral earth arrange- ments (isolated, resonant-earthed, through resistor or direct earthed). Suitable to Enel DK5600 requirements s Types with undervoltage (27) and T T live line monitoring (59T) functions li li li are available. a a , They may be utilized as voltage T T . control in load shedding and auto- c c matic repowering of transformers. m m

Protection & control functions 27 Undervoltage

52 SSG

50/51 Phase overcurrent

74TCS BF

50N/51N Residual overcurrent 59N Residual overvoltage

59T27

59T Live line monitoring

67 50 51

67 Directional overcurrent 67N Directional ground fault

59N METERING-

Blocking Logic selectivity

I .. I , I .., I , U , ϕ ..- Events 1...8 - Signal recording 67N 50N51N L1 L3 θL 1 E E E

BF Breaker failure TCS Trip circuit supervision

Control functions & Logic selectivity COMMUNICATION- Modbus RS485- RS232

Inhibition Inrush block Two setting profiles Measuring inputs

The relay protection functions have two setting parameters configu-rations (BANK A or BANK B). Activation of the two data sets is con- trolled by logical input or communications interfaces. Three phase current inputs and one residual current input, with nominal currents independently selectable at 1A or 5 A (different order codes to select). Three phase voltage inputs and one residual voltage input.

Construction

Flush or projecting mounting; current measuring circuits provided with short-circuiting devices.

Breaker failure

The Breaker failure function (BF) may be associated to all SSG pro- tection thresholds.