Article 314 — Boxes and Fittings (continued)
16(A)
Table 314.16(B)
Volume Allowance Required per Conductor
Metal Boxes
3
BOX TRADE SIZE MM (IN.)
MINIMUM VOLUME CM3 IN.3
MAXIMUM NUMBER OF CONDUCTORS* 18 16 14 12 10 8 6
100 x 32 (4 x 1J4) Round/Octagonal
205 12.5
8 7 6 5 5 5 2
100 x 38 (4 x VA) Round/Octagonal
254 15.5
10 8 7 6 6 5 3
100 x 54 (4 x 2^ Round/Octagonal
353 21.5
14 12 10 9 8 7 4
100 x 32 (4 x 1!4 Square
295 18.0
12 10 9 8 7 6 3
100 x 38 (4 x 1!/!) Square
344 21.0
14 12 10 9 8 7 4
100 x 54 (4 x 2^ Square
497 30.3
20 17 15 13 12 10 6
120 x 32 (4L x 114) Square
418 25.5
17 14 12 11 19 8 5
120 x 38 (4L x 112) Square
484 29.5
19 16 14 13 11 9 5
120 x 54 (4L x 218) Square
689 42.0
28 24 21 18 16 14 8
75 x 50 x 38 (3 x 2 x 1$ Device
123 7.5
5433321
75 x 50 x 50 (3 x 2 x 2) Device
164 10.0
6 5 5 4 4 3 2
75 x 50 x 57 (3 x 2 x 2$ Device
172 10.5
7654432
75 x 50 x 65 (3 x 2 x 2$ Device
205 12.5
8765542
75 x 50 x 70 (3 x 2 x 2^ Device
230 14.0
9876542
75 x 50 x 90 (3 x 2 x 3$ Device
295 18.0
12 10 9 8 7 6 3
100 x 54 x 38(4 x 7Ax 1$ Device
169 10.3
6554432
100 x 54 x 48(4 x 7Ax 1$ Device
213 13.0
8765542
100 x 54 x 54(4 x 2Ax 2^ Device
238 14.5
9876542
95 x 50 x 65 (3%x 2 x 2A) Masonry Box/Gang
230 14.0
9876542
95 x 50 x 90 (3%x 2 x 3A) Masonry Box/Gang Min. 44.5 depth FS - Single Cover/Gang (1 $
244 21.0 221 13.5
14 12 10 9 8 7 2 9766542
Min. 60.3 depth FD - Single Cover/Gang (2$
295 18.0
12 10 9 8 7 6 3
Min. 44.5 depth FS - Multiple Cover/Gang (1 ^
295 18.0
12 10 9 8 7 6 3
Min. 60.3 depth FD - Multiple Cover/Gang (2$
395 24.0
16 13 12 10 9 8 4
SIZE OF CONDUCTOR
FREE SPACE WITHIN BOX FOR EACH CONDUCTOR
(AWG)
CM3
IN.3
No. 18
24.6
1.50
No. 16
28.7
1.75
No. 14
32.8
2.00
No. 12
36.9
2.25
No. 10
41.0
2.50
No. 8
49.2
3.00
No. 6
81.9
5.00
Reprinted with permission from National Fire Protection Association 70-1987. National Electrical Code, Copyright© 1986, National Fire Protection Association, Quincy, MA 02269.
s
This reprinted material is not the complete and official position of the NFPA on the referenced subject which is represented only by the standard in its entirety. NEC® is a registered trademark of the National Fire Protection Association, Inc., Quincy, MA 02269.
Underwriters Laboratories Inc. File Number: E2969 (U.L. 514A) Canadian Standards Association File Number: LR 12798
Federal Manufacture Number: 56501
Products designed to meet Federal Specification Number: A-A5924 (formerly W-J-800). Verification of file numbers and compliance with federal specifications for individual items available upon request.
Box and cover material and plating specification; .062" minimum thickness,
hot rolled, pre-galvanized steel, minimum spangle.
ASTM G-60-U, AISI C-1008
Bracket material: All brackets except MS style; 16 gauge (.060") hot rolled, pre-galvanized steel AISI C-1008, G-60-U. MS Style bracket; 20 gauge (.036") cold rolled spring steel AISI C-1055, heat treated to R. 35 zinc plated .0005 thick.
*Where no volume allowances are required by 314.16(B)(2) through 314.16(B)(5).
Underwriters Laboratories Inc. File Number: E2969 (U.L. 514A)
Canadian Standards Association File Number: LR 12798
Federal Manufacture Number: 56501 (Cage Code)
Products designed to meet Federal Specification Number: W-J-800
Verification of file numbers and compliance with federal specifications for individual items
available upon request.
Box and cover material and plating specification; .062" minimum thickness, hot rolled, pre-galvanized steel, minimum spangle.
ASTM G-60-U, AISI C-1008
Bracket material: All brackets except MS style; 16 gauge (.060") hot rolled, pre-galvanized steel AISI C-1008, G-90-U. MS style bracket; 20 gauge (.036") cold rolled spring steel AISI C-1055, heat treated to R. 35 zinc plated .0005 thick.
Metallic Boxes — Fire Resistance Rating
Wall Penetrations
Listed single and double gang metallic outlet and switch boxes and octagon ceiling boxes with metallic or non-metallic cover plates may be used in
bearing and non-bearing wood stud and steel stud walls with ratings not
exceeding 2 hours. These walls shall have gypsum wallboard facings similar to those shown in Design Nos. U301, U411, and U425. 4 in. square boxes may be used in 2 hr. fire rated ceilings.
The surface area of individual metallic outlet or switch boxes shall not exceed 16 sq. in. The aggregate surface area of the boxes shall not exceed 100 sq. inches per 100 sq. ft. of wall. Boxes located on opposite sides of walls or partitions shall be separated by a horizontal distance of 24 inches.
The metallic outlet or switch boxes shall be securely fastened to the studs and the opening in the wallboard facing shall be cut so that the clearance between the box and the wallboard does not exceed % in.