Recirculating Chillers

NESLAB Merlin SeriesRecirculating Chillers

Delivers a continuous supply of cooling capacity up to 5045 watts. The NESLAB Merlin Series recirculating chillersprovide a wide range of cooling capacity all in a highly reliable, space-saving package for your critical application needs.
NESLAB Merlin Series Recirculating Chillers

System Specifications

M 25M 33 M 75M 100M 150Cooling capacity @ 20°C60 Hz810 watts1250 watts2410 watts3500 watts5045 watts2765 BTU4266 BTU8225 BTU 11946 BTU17219 BTU 697 Kcal 1075 Kcal2073 Kcal3010 Kcal4339 Kcal50 Hz725 watts1125 watts2180 watts3500 watts4540 watts2474 BTU3840 BTU7440 BTU 11946 BTU15495 BTU 624 Kcal 968 Kcal1875 Kcal3010 Kcal3905 Kcal RefrigerantR134AR134AR134AR404AR404ATemperature range standard+5°C to 35°C+5°C to 35°C+5°C to 35°C+5°C to 35°C+5°C to 35°Clow temperature option-15°C to 35°C-15°C to 35°C-15°C to 35°C-15°C to 35°C-15°C to 35°CTemperature stability+/- 0.1°C+/- 0.1°C+/- 0.15°C+/- 0.15°C+/- 0.15°C Pumps MD 30 – Mag Drive*yesyesn/an/an/aPD 1 – Positive Displacementyesyesyesn/an/aPD 2 – Positive Displacementn/ayesyesyesyesCP 55 – Centrifugal Pumpn/an/an/ayes**yes**Reservoir volumegallon0.50.50.50.50.5 liter1.81.81.81.81.8Unit dimensionsH x W x D in23.50 x 12.62 x 20.8523.50 x 12.62 x 20.87526.125 x 16.25 x 2430.375 x 21.25 x 29.2530.375 x 21.25 x 29.25 H x W x D cm59.7 x 32.1 x 53.059.7 x 32.1 x 53.066.4 x 41.3 x 61.077.2 x 54.0 x 74.377.2 x 54.0 x 74.3Power requirementsoption 1115V, 60 Hz, 10 amps115V, 60 Hz, 13 amps200-230V, 60 Hz, 9 amps200-230V, 60 Hz, 13 amps200-230V, 60 Hz, 15 amps 100V, 50 Hz, 10 amps100V, 50 Hz, 13 amps200V, 50 Hz, 9 amps200V, 50 Hz, 13 amps200V, 50 Hz, 15 ampsoption 2230V, 50 Hz, 5 amps200-230V, 60 Hz, 7 amps230, 50 Hz, 9 amps230V, 50 Hz, 13 amps230V, 50 Hz, 16 amps 200V, 50 Hz, 7 amps option 3n/a230, 50 Hz, 7 ampsn/a400V, 50 Hz, 3 ph 8 amps400V, 50 Hz, 3 ph 8 ampsUnit weightlb118120176254254 kg545480115115Compliance60 HzUL/cUL, CEUL/cUL, CEUL/cUL, CEUL/cUL, CEUL/cUL, CE 50 HzUL/cUL, CEUL/cUL, CEUL/cUL, CECECE
Specification listed for standard units circulating water at 20°C fluid temperature and 20°C ambient. Other fluids, fluid temperatures, or ambienttemperatures will affect performance. Cooling capacity and amperage ratings based on units with PD 1 pumps (PD 2 with M 100 and M 150). Other pumpswill affect performance. Specifications are subject to change. *Available in 60 Hz configuration only. **M 100 and M 150 units with CP 55 pump have a height of 36.4”, and unit weight of 275 lbs.

18

Customer Service: 1-800-258-0830 • Web Address: www.thermo.com/tc
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36