Catalogue Stationary Solutions for Air Conditioning and Process
www.testo.com
print switch display
Page / 120
TESTO - 2088, 2090, 164960, 157537
/ 120
See other catalogues for TESTO
Text version of the page
11
Axx
Bxx
Cxx
Fxx
Gxx
Mxx
Kxx
M01 Stainless steel sintered filter
M02 Metal wire protection cap
M03 Teflon sintered filter
M04 Metal protection cap, open
M05 Plastic cap ABS (open)
\- only for A02
A01 Wall version A02 Duct version
K01 K02 K03 K04 K05
K06 K07
IM German-English IM French-English IM Spanish-English IM Italian-English IM Dutch-English IM Japanese-English IM Chinese-English
B01 4 to 20 mA(2 wire, 24 VDC)*
B02 0 to 1 V (4 wire, 24 VAC/DC)
B03 0 to 5 V (4 wire, 24 VAC/DC)
B04 0 to 10 V (4 wire, 24 VAC/DC)
Two analog outputs each
Language versions ■ of Instruction Manuals
C00 Without display C01 With display
Ordering examples:
1. Duct version with 0 to 10 V outputs, with display, %RH, °C, open plastic cap, German-English Instruction Manual
— 0555 6621 / A02 / B04 / C01 / F01 / G02 / M05 / K01
2. Wall version with 0 to 1 V outputs, without display, %RH, °F, Italian-English Instruction Manual
— 0555 6621 / A01 / B02 / C00 / F01 / G03 / K04
F01 Relative humidity (%RH)
G02 Temperature (°C) G03 Temperature (°F)
*not available for wall version A01
Overview of Product Line
testo 6621 A01 / ... / C01 / ... Wall version with display
testo 6621 A02 / ... / C01 / ...
Duct version with display
m
testo 6621 A01 / ... / C00 / ...
Wall version without display
M
testo 6621 A02 / ... / C00 / ...
Duct version without display
Type
testo 6621 - A01 (wall version)
testo 6621 - A02 (duct version)
Sensor
Output parameters
Relative humidity %RH as well as temperature °C or °F (two separate analog outputs)
Measurement ranges (rel. humidity/temperature)
0 to 100 %RH (not for high humidity processes) 0 to +60 °C(32 to+140 °F)
0 to 100 %RH (not for high humidity processes) -20 to+70 °C (-4 to+158 °F)
Measurement medium, Pressure range
Air in air conditioning units or rooms, max. 1 bar positive pressure
Measurement inaccuracy/Humidity
±2.5% (0 to 90 %RH), ±4% (90 to 100 %RH) Temperature coefficient: 0.05% / K (difference of 25 °C)
±2.5% (0 to 90 %RH), ±4% (90 to 100 %RH) Temperature coefficient: 0.05% / K (difference of 25 °C)
Measurement inaccuracy/Temperature
±0.5 °C/ 0.9 °F
±0.5 °C/ 0.9 °F
Replaceability of humidity sensor
By Testo Service Department
Can be replaced by customer (see below for spare sensor), 2-point adjustment subsequently required
Analog outputs (two channels each)
Current output: 4 to 20 mA ±0.05 mA as 2-wire version (not for wall version) or voltage output: 0 to 1 VDC ±2.5 mV; 0 to 5 VDC ±12.5 mV; 0 to 10 V ±25 mV as 4-wire version (please order accordingly, no on-site adaptation)
Display, resolution and measurement rate
2 line LCD (optional) humidity resolution: 0.1 %RH, temperature resolution: 0.1 °C/ 0.1 °F, measurement rate 1/s
Power supply
At voltage output: 20 to 30 VDC / VAC
At voltage output: 20 to 30 VDC / VAC
Housing material + Dimensions
ABS, 81 x 81 x 26 mm
ABS, 81 x 81 x 42 mm, refer to diagram for probe
Temperature application range (housing)
-20 to +70 °C (-4 to+158 °F)
With display: 0 to +50 °C (32 to +122 °F)
-20 to+70 °C (-4 to+158 °F)
With display: 0 to +50 °C (32 to +122 °F)
Storage temperature
-40 to +80 °C (-40 to +176 °F)
-40 to +80 °C (-40 to +176 °F)
Cable screw connections
None (cable is through back wall opening or break-out opening on underside
1 x M16 x 1.5
Weight, IP protection
80 g, IP 30
160 g, IP 65
EMC
In accordance with EU guideline 89/336/EEC
In accordance with EU guideline 89/336/EEC
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-120