| | | f3j@|0 Sensing & Monitoring Relays Series ENYA | | |
| | | |
| | | Automation components Level monitoring | | |
| | | |
| | | Level monitoring of conductive liquids Multifunction Reinforced insulation of the measuring circuit 1 CO contact Width 35mm Installation design | | |
| | | |
| | | --------- | | |
| | | |
| | | Art.No. (PQ1) Art.No. (PQ10) EAN13-Code | | |
| | | 1341500 | | |
| | | |
| | | 900866200509 | | |
| | | |
| | | Measured variable | | conductiv probe min. conductiv probe max. | | |
| | | |
| | | |
| | | Measured range Probe voltage Probe current Wiring distance | | 0,25 to 100kO | | |
| | | |
| | | 12V AC | | |
| | | |
| | | max. 7mA | | |
| | | |
| | | max. 1000m (adjustment <50%) max. 100m (adjustment <100%) capacity of cable 100nF/km | | |
| | | |
| | | |
| | | Control | | Delay ON • Delay OFF • Sensitivity • Function | | |
| | | |
| | | |
| | | Indicators (LEDs) | | |
| | | U • R | | |
| | | |
| | | |
| | | Pump up Pump down | | |
| | | |
| | | 0,25 to 100 kO (Sensitivity) | | |
| | | trigger level Tripping delay Turn-off delay Supply | | |
| | | |
| | | 0,5s to 10s | | |
| | | |
| | | 0,5s to 10s | | |
| | | |
| | | 230VAC terminals A1-A2 | | |
| | | |
| | | |
| | | Output | | 1 CO contact 250V, 5A AC | | |
| | | |
| | | |
| | | Width | | 35mm | | |
| | | |
| | | Certificates Mechanical design Terminal capacity | | CE | | |
| | | |
| | | Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 according to EN 50022 • Mounting position any • Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm 1 x 0,5 to 2,5mm2 with/without multicore cable end • 1 x 4mm2 without multicore cable end • 2 x 0,5 to 1,5mm2 with/without multicore cable end • 2 x 2,5mm2 flexible without multicore cable end Ambient temperature: -25 to +55°C (according to IEC 68-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) • Pollution degree: 2, if built in 3 (according to IEC 664-1) • Vibration resistance: 10 to 55Hz 0,35mm (according to IEC 68-2-6) • Shock resistance: 15g 11ms (according to IEC 68-2-27) | | |
| | | |
| | | Ambient conditions | | |
| | | |
| | | |
| | | Accessories | | |
| | | |
| | | www.tele-power-net.com | | Page 51 | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |