TELE Catalogue - Tele Haase Steuergeräte - #39

/ 208


catalogue search
P. 01
P. 02
P. 03
P. 04
P. 05
P. 06
P. 07
P. 08
P. 09
P. 10
P. 11
P. 12
P. 13
P. 14
P. 15
P. 16
P. 17
P. 18
P. 19
P. 20
P. 21
P. 22
P. 23
P. 24
P. 25
P. 26
P. 27
P. 28
P. 29
P. 30
P. 31
P. 32
P. 33
P. 34
P. 35
P. 36
P. 37
P. 38
P. 39
P. 40
P. 41
P. 42
P. 43
P. 44
P. 45
P. 46
P. 47
P. 48
P. 49
P. 50


See other catalogues for Tele Haase Steuergeräte

Text version of the page
fj|@|0 Sensing & Monitoring Relays Series GAMMA
Automation components Level monitoring
Level monitoring of conductive substances
Pump up or minimum monitoring
Pump down or maximum monitoring
Secure galvanic separation of measuring circuit
2 CO contacts
Width 22,5mm
Industrial design
Art.No. (PQ1)
2390201
2390202
2390200
Art.No. (PQ10)
-
-
-
EAN13-Code
900866200254
900866200255
900866200253
Measured variable
conductiv probe min. conductiv probe max.
conductiv probe min. conductiv probe max.
conductiv probe min. conductiv probe max.
Measured range
0,25 to 100kO
0,25 to 100kO
0,25 to 100kO
Probe voltage
max. 16VAC
max. 16VAC
max. 16VAC
Probe current
max. 7mA
max. 7mA
max. 7mA
Wiring distance
max. 1000m (adjustment <50%) max. 100m (adjustment <100%)
max. 1000m (adjustment <50%) max. 100m (adjustment <100%)
max. 1000m (adjustment <50%) max. 100m (adjustment <100%)
capacity of cable 100nF/km
capacity of cable 100nF/km
capacity of cable 100nF/km
Delay on • Delay off • Sensitivity • Function
Delay on • Delay off • Sensitivity • Function
Delay on • Delay off • Sensitivity • Function
U • R
U • R
U • R
Pump up Pump down
Pump up Pump down
Pump up Pump down
trigger level
0,25 to 100 kO (Sensitivity)
0,25 to 100 kO (Sensitivity)
0,25 to 100 kO (Sensitivity)
0,5s to 10s
0,5s to 10s
0,5s to 10s
0,5s to 10s
0,5s to 10s
0,5s to 10s
Supply
24VAC terminals A1-A2
110VAC terminals A1-A2
230VAC terminals A1-A2
2 CO contacts
250V, 5A AC
2 CO contacts
250V, 5A AC
2 CO contacts 250V, 5A AC
Width
22.5mm
22.5mm
22.5mm
Cerates
CE•UL•cUL • GOST
CE•UL•cUL • GOST
CE•UL•cUL • GOST
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 according to EN 50022 terminal connection according to VBG 4 (PZ1 required) • IP rating IP20 • Tightening torque max. 1Nm.
Mounting position any • Shockproof
1 x 0,5 to 2,5mm2 with/without multicore cable end
2 x 2,5mm2 flexible without multicore cable end
• 1 x 4mm2 without multicore cable end • 2 x 0,5 to 1,5mm2 with/without multicore cable end •
Ambient temperature: -25 to 55°C (according to IEC 68-1); -25 to 40°C (according to UL 508) • Storage temperature: -25 to +70°C •
Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) • Pollution degree: 3 (according to IEC
60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (according to IEC 68-2-6) • Shock resistance: 15g 11ms (according to IEC 68-2-27)
conductive probes (types SK1, SK2, SK3) • sealable intervention protection shield FA-G2
www.tele-power-net.com
Page 39