| | Art.No. (PQ1) | 2390201 | 2390202 | | 2390200 | |
| | Art.No. (PQ10) | - | - | | - | |
| | EAN13-Code | 900866200254 | 900866200255 | | 900866200253 | |
| | Measured variable | conductiv probe min. conductiv probe max. | conductiv probe min. conductiv probe max. | | conductiv probe min. conductiv probe max. | |
| | Measured range | 0,25 to 100kO | 0,25 to 100kO | | 0,25 to 100kO | |
| | Probe voltage | max. 16VAC | max. 16VAC | | max. 16VAC | |
| | Probe current | max. 7mA | max. 7mA | | max. 7mA | |
| | Wiring distance | max. 1000m (adjustment <50%) max. 100m (adjustment <100%) | max. 1000m (adjustment <50%) max. 100m (adjustment <100%) | | max. 1000m (adjustment <50%) max. 100m (adjustment <100%) | |
| | | capacity of cable 100nF/km | capacity of cable 100nF/km | | capacity of cable 100nF/km | |
| | | Delay on • Delay off • Sensitivity • Function | Delay on • Delay off • Sensitivity • Function | Delay on • Delay off • Sensitivity • Function | |
| | | U • R | U • R | | U • R | |
| | | Pump up Pump down | Pump up Pump down | | Pump up Pump down | |
| | trigger level | 0,25 to 100 kO (Sensitivity) | 0,25 to 100 kO (Sensitivity) | | 0,25 to 100 kO (Sensitivity) | |
| | | 0,5s to 10s | 0,5s to 10s | | 0,5s to 10s | |
| | | 0,5s to 10s | 0,5s to 10s | | 0,5s to 10s | |
| | Supply | 24VAC terminals A1-A2 | 110VAC terminals A1-A2 | | 230VAC terminals A1-A2 | |
| | | 2 CO contacts 250V, 5A AC | 2 CO contacts 250V, 5A AC | | 2 CO contacts 250V, 5A AC | |
| | Width | 22.5mm | 22.5mm | | 22.5mm | |
| | Cerates | CE•UL•cUL • GOST | CE•UL•cUL • GOST | | CE•UL•cUL • GOST | |
| | | Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 according to EN 50022 terminal connection according to VBG 4 (PZ1 required) • IP rating IP20 • Tightening torque max. 1Nm. | Mounting position any • Shockproof | |
| | | 1 x 0,5 to 2,5mm2 with/without multicore cable end 2 x 2,5mm2 flexible without multicore cable end | • 1 x 4mm2 without multicore cable end • 2 x 0,5 to 1,5mm2 with/without multicore cable end • | |
| | | Ambient temperature: -25 to 55°C (according to IEC 68-1); -25 to 40°C (according to UL 508) • Storage temperature: -25 to +70°C • Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) • Pollution degree: 3 (according to IEC 60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (according to IEC 68-2-6) • Shock resistance: 15g 11ms (according to IEC 68-2-27) | |
| | | conductive probes (types SK1, SK2, SK3) • sealable intervention protection shield FA-G2 | |
| | | | | | | |