f3j@|0 Sensing & Monitoring Relays Series GAMMA
Automation components Voltage monitoring in 3-phase mains + neutral
■ Multifunction
■ Monitors phase to neutral voltages
■ Fault latch
■ Connection of neutral wire necessary
■ Supply voltage selectable via PowerModules
■ 2 CO contacts
■ Width 22,5mm
■ Industrial design
---------
Art.No. (PQ1)
2390508
Art.No. (PQ10)
-
EAN13-Code
900866200285
Measured variable
3N~
AC Sinus (48 to 63Hz)
Measured range
UN = 400/230V terminals N-L1-L2-L3
Controls
max • min • Delay • Function
Indicators (LEDs)
U • max • min • R
Functions
OVER OVER+LATCH
UNDER UNDER+LATCH WIN WIN+LATCH
Asymmetry
-
Switching threshold max. Switching threshold min.
Tripping delay Start-up suppression time Fault latch Supply
-20% to 30% from U„
-30% to 20% from U„
0,1s to 10s
selectable
PowerModule TR2 terminals A1-A2
Output
2 CO contacts 250V, 5A AC
Width
Certificates
Mechanical design
Terminal capacity
22,5mm
CE•UL•cUL • GOST
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 according to EN 50022 • Mounting position any • Shockproof terminal connection according to VBG 4 (PZ1 required) • IP rating IP20 • Tightening torque max. 1Nm.
1 x 0,5 to 2,5mm2 with/without multicore cable end • 1 x 4mm2 without multicore cable end • 2 x 0,5 to 1,5mm2 with/without multicore cable end •
2 x 2,5mm2 flexible without multicore cable end
Ambient temperature: -25 to 55°C (according to IEC 68-1); -25 to 40°C (according to UL 508) • Storage temperature: -25 to +70°C •
Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) • Pollution degree: 3 (according to IEC
60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (according to IEC 68-2-6) • Shock resistance: 15g 11ms (according to IEC 68-2-27)
Ambient conditions
PowerModule TR2 (12 to 400V AC) • sealable intervention protection shield FA-G2
Accessories
www.tele-power-net.com
Page 19