Automation Components
Sensing & Monitoring Relays Series GAMMA
Voltage monitoring in 3-phase mains Multifunction
Monitoring of phase sequence and phase failure Asymmetry detection switchable Connection of neutral wire optional Detection of loss of neutral wire Fault latch (G4PM)
Supply voltage selectable via PowerModules or by zoom voltage 24 to 240V AC/DC
1 CO contact; 2 CO contacts
Width 22,5mm or 45mm; Industrial design
G2PM400VSY20 24-240V
G4PM690VSYL20
4PM500VSYL
G2PM400VSY20
G2PM400VSY10
Art.No. (PQ1) Art.No. (PQ10) EAN13-Code Measured variable
Measured range
2394500
2394501
2390505
2390504
2390500
-
-
-
-
-
900866200296
900866200297
900866200284
900866200281
900866200276
3(N)~ AC Sinus (48 to 63Hz)
3(N)~ AC Sinus (48 to 63Hz)
3(N)~
AC Sinus (48 to 63Hz)
3(N)~ AC Sinus (48 to 63Hz)
3(N)~ AC Sinus (48 to 63Hz)
UN = 690/400V terminals (N)-L1-L2-L3
UN = 500V terminals (N)-L1-L2-L3
UN = 400/230V terminals (N)-L1-L2-L3
UN = 400/230V terminals (N)-L1-L2-L3
UN = 400/230V terminals (N)-L1-L2-L3
ASYM • max • min • Delay • Function
ASYM • max • min • Delay • Function
ASYM • max • min • Delay • Function
ASYM • max • min • Delay • Function
ASYM • max • min • Delay • Function
ASYM • max • min • SEQ • R
ASYM • max • min • SEQ • R
ASYM • max • min • SEQ • R
ASYM • max • min • SEQ • R
ASYM • max • min • SEQ • R
UNDER UNDER+SEQ WIN WIN+SEQ UNDER+LATCH UNDER+SEQ+LATCH WIN+LATCH WIN+SEQ+LATCH
UNDER
UNDER+SEQ WIN WIN+SEQ UNDER+LATCH UNDER+SEQ+LATCH WIN+LATCH WIN+SEQ+LATCH
UNDER
UNDER+SEQ WIN WIN+SEQ
UNDER
UNDER+SEQ WIN WIN+SEQ
UNDER
UNDER+SEQ WIN WIN+SEQ
5% to 25% • Off
5% to 25% • Off
5% to 25% • Off
5% to 25% • Off
5% to 25% • Off
-20% to 30% from UN
-20% to 30% from UN
-20% to 30% from UN
-20% to 30% from UN
-20% to 30% from UN
-30% to 20% from UN
-30% to 20% from UN
-30% to 20% from UN
-30% to 20% from UN
-30% to 20% from UN
0,1s to 10s
0,1s to 10s
0,1s to 10s
0,1s to 10s
0,1s to 10s
-
-
-
-
-
selectable
selectable
-
-
-
PowerModule TR3 terminals A1-A2
PowerModule TR3 terminals A1-A2
24 to 240V AC/DC
terminals A1-A2
PowerModule TR2 terminals A1-A2
PowerModule TR2 terminals A1-A2
2 CO contacts; 250V, 5A AC
2 CO contacts; 250V,
5A AC
2 CO contacts; 250V,
5A AC
2 CO contacts; 250V,
5A AC
1 CO contact
250V, 5A AC
45mm
45mm
22,5mm
22,5mm
22,5mm
CE •UL•cUL
CE • UL•cUL
CE•UL•cUL • GOST
CE • UL • cUL • GOST
CE•UL•cUL • GOST
Indicators (LEDs)
Asymmetry Switching threshold max. Switching threshold min.
Tripping delay Start-up suppression time Fault latch Supply
Output
Width Certificates
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 according to EN 50022 • Mounting position any • Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm
1 x 0,5 to 2,5mm2 with/without multicore cable end • 1 x 4mm2 without multicore cable end • 2 x 0,5 to 1,5mm2 with/without multicore cable end •
2 x 2,5mm2 flexible without multicore cable end
Ambient temperature: -25 to 55°C (according to IEC 68-1); -25 to 40°C (according to UL 508) • Storage temperature: -25 to +70°C •
Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) • Pollution degree: 3 (according to IEC
60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (according to IEC 68-2-6) • Shock resistance: 15g 11ms (according to IEC 68-2-27)
Mechanical design
Terminal capacity
Ambient conditions
PowerModules TR2 (12 - 400V AC) and TR3 (12 - 500V AC) • sealable intervention protection shield FA-G2
Accessories