34
Specifications
Battery Input
90 to 180 VDC, 3VA - For 125V battery
Ground Resistors
30K ħ1% from each bus to ground
Voltage Indication
0 to ħ199.9 VDC in 0.6 bright red LED digit
and decimal point accuracy is ħ0.2 VDC
Ranges
Ħ +Bus to Ground (+GND)
Ħ -Bus to Ground (- to GND)
Ħ Ground Fault Voltage (Fault)
Ħ Battery Voltage (BAT)
Scanning
Each range is automatically scanned and
read every three seconds.
Alarms
Ħ The +/- Fault relay energizes and
latches when the + fault voltage exceeds
the +/- set value for the time setting. The
alarm LED lights. Set range is 13.0 to
100.0V
Ħ Hi Battery and Low Battery relays
energize and latch when the battery
voltage exceeds the Hi or Low set
value for the time setting. (Hi set range
is 125.0 to 150.0V, and the Low set
range is 100.0 to 125.0V)
BATTERY MONITORING EQUIPMENT
Portable Battery Monitor / Ground Fault Locator
Voltage/Ground Meter/Alarm Relays
Switchboard Meters
DC Battery Voltage Meters
SBSs Battery Monitor is a breakthrough in ground fault detection. This full Battery Voltage/Ground Meter/
Alarm Relay automatically indicates the instant a ground occurs. The optional hand-held ground fault locator
finds the exact location of that ground, no matter where it is in the line.
This highly accurate DC voltage meter relay provides voltage readings of battery, + or -BUS to ground,
and ground fault voltages for protection of the essential BUS. The ground fault relays indicate the ground
anywhere in the system, whether on the + or the - side. Over/Under Voltage relays are provided. Fail
safe operation of the under voltage relay operates correctly down to zero volts. Time delay, which can be set
from 5 to 60 seconds, is provided to avoid nuisance alarms.
50-469-BB
Fault Indicator Specifications
Ħ Operation - Hand-activated on-off
button/switch
Ħ Features - Automatic selection of
grounded line. Does not interfere with
sensitive electronic equipment, radio, etc.
Ħ Receiver - Does not contact circuitry;
LED and sound indicators
Ħ Sensitivity - Up to 100Ù resistance
Time Delay
Can be set from 5 to 60 seconds
Reset
Panel push button or remote contact closure
will reset an alarm provided the cause is
removed
Contact Rating
2A at 120 VAC or 28 VDC
Limit Setting
Limits and time delay are set by removing
the front bezel (4 screws). This can safely be
done with power on.
Optional Fault
Indicator (-BB) Information
Operation:
Produces current pulses between the
transmitter and the ground fault. A pulse
receiver can trace the line with these pulses
to the ground. Circuit breaker in the line can
be identified and open to clean the ground
from the system.
Features:
Ħ On/off switch on front panel
Ħ Automatic selection of grounded line
Ħ Does not interfere with sensitive
electronic equipment, radio, etc.
Optional Hand Held Receiver:
Part No. 200A
Ħ Does not contact circuitry
Ħ LED and sound indications
Ordering Information
Part No. Description
25-469 125Vdc battery voltage meter
25-471 48Vdc battery voltage meter
25-472 250Vdc battery voltage meter
200A Handheld receiver, suffix -BB is required
Accessory Ordering Information
Suffix Description
-BB Optional fault indicator added to voltage meter
-J3.0 Digital RS323/485 with DNP3.0 or Modbus
-1420 4 to 20 mADC, 1% accuracy
-101 0 to 1 mADC, 0.1 accuracy
Ordering Information
Part No. Description
50-469-BB 125Vdc portable battery monitor
Additional Voltages
50-471-BB 48Vdc portable battery monitor
50-472-BB 250Vdc portable battery monitor
Accessory Ordering Information
Suffix Description
-J3.0 Digital Rs232/485 with DNP3.0 or Modbus
-1420 4 to 20 mADC, 1% accuracy
-101 0 to 1 mADC, 0.1 accuracy
|
|