Axiom8
rBiiit'
valve communication and control
Diagnostic Systems
Reduce plant down time and cut maintenance costs with AS-Interface diagnostics.
The AMI96 model features optional on-board diagnostic systems which may predict potential automated valve malfunctions. As a result, plant down time may be reduced by repairing discrete automated valves which, when called upon to operate, would have failed to do so. And, should problems occur during normal operation, maintenance personnel will be aided in rapidly locating failure causes thus reducing maintenance time and speeding valve repair and operation renewal.
Diagnostic Alerts & Capabilities
• Low pneumatic supply pressure
Should supply pressure drop below operational threshold level a local and remote alert will be activated.
• Malfunctioning solenoid
A shorted or opened solenoid circuit will be identified during operation with a local and remote alert.
• Stuck pneumatic spool or pilot valve
Should either the pilot poppet or main spool be stuck for any reason (air line contamination, freezing etc.) a local and remote alert will be energized.
• Stuck process valve/actuator
If the Axiom stalls in mid stroke and no on-board problem sources are identified an alert will be energized locally and remotely that the problem source is located in the valve/actuator assembly.
• Remote switch setting
Open and Closed limit switch settings may be made with on-board push buttons or remotely through the control system.
• Identification "winking"
To positively confirm the field device identity the control room may initiate the "wink" function which flashes both open and closed LEDs without affecting valve operational status.
Alerts are cleared automatically when normal operating conditions are restored.
Control System Interface
AS-Interface 2.1 or greater level protocol may be used to interface up to 31 Axiom units into the control system. Communication bits may be mapped into standard DCS or PLC as desired. No special software is required. See StoneL FieldLink program for information about the cost saving benefits and easy installation of the AS-Interface protocol.
Control Room
Diagnostic Specifications
Protocol
AS-Interface (AMI96) Version 2.1 or greater
Input Voltage
26.5 to31.6VDC (AS-i power supply)
Devices per Network Input Configuration
Output Configuration
31
(1) Open & (1) Closed
(1) LowSupply Pressure
(1) Bad Solenoid Coil or Stuck
Spool/Pilot Valve* (1) Stuck Process Valve/Actuator (1) Solenoid Power 0.5 W @ 24VDC (1) Wink Operation (1) Remote Set Open (1) RemoteSet Closed
Pressure Accuracy
± 2 psi (0.13 bar)
Supply Pres. Default
40 psi (2.7 bar) minimum
System Interface
AS-Ì2.1 masterorgreater required
* Local display identifies specific problem.
7
StoneL Corporation Phone: (218) 739-5774 • Toll-free: (800) 843-7866 • Website: www.stonel.com
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
pdf-page pdf di En 2008-10-42-14