Text version of the page
2
Safety BarriersSeries 9001, 9002
Standard Applications
Selection table Description Ordering code ApplicationPt100, 2-wire-connection Field circuit floating Diagram 9002/22-093-300-0019002/22-032-300-111 >
09959E02 Nominal values Operating voltageU >
N ( 1.4 VEnd-to-end resistance of the safety barrierR = 2 x (20 O ± 0.1 O )Measuring range ( 400 °C (I >
N ( 5 mA) ( 850 °C (I >
N ( 3 mA) Safety values Maximum voltageU >
o = 3.2 VMaximum currentI >
o = 300 mAMaximum permissible external inductanceL IIC
0.2 mHIIB1.8 mHMaximum permissible external capacitanceC >
o m FIIB1000 m F IIC
100 >
o ApplicationPt100, 3-wire-connection Field circuit floating Diagram 9002/22-032-300-1119001/02-016-150-111 >
09960E02 Nominal values Operating voltageU >
N ( 1.4 VEnd-to-end resistance of the safety barrierR = 2 x (20 O ± 0.1 O )Measurement range ( 400 °C (I >
N ( 5 mA) Maximum voltageU ( 850 °C (I >
N ( 3 mA) Safety values >
o = 3.2 VMaximum currentI >
o = 450 mAMaximum permissible external inductanceL IIC
0.12 mHIIB0.5 mHMaximum permissible external capacitanceC >
o m FIIB1000 m F IIC
100 >
o 2/7