SOLID
Applied Technologies Ltd.
MonoScan/MicroScan - 5P Installation tips Power-Pipes-Positioning-Programming-Physics
Power
Voltage
MUST BE
12 Volts or more on the terminals.
A battery
MUST BE
rated higher than 12 Volts due to normal voltage drop.
Rechargeable supply
MUST BE
non operational when switched to recharge.
PLC connections
MUST BE
as specified in the user manual, preferably grounded.
Pipes
Extension pipes
MUST BE
of internal diameter 3.5" min and length of 25 cm max.
Extension pipes
MUST BE
preferably plastic and non-perturbing into the tank.
Positioning
Distance to tank walls
MUST BE
at least 50 cm. Add 10 cm spacing for each 1m in range.
sensor
MUST BE
exactly perpendicular to the surface of target.
Programming
Tank height, level/distance
MUST BE
configured correctly.
SBD
MUST BE
configured in flange / extension pipe based installations.
Interfering signals
MUST BE
defined when tank is empty.
Physics
Acoustic noise and vibrations
MUST BE
minimized, reducing interference with echoes.
Physical obstacles and dust
MUST BE
absent along the echo path.
Electrical interference
MUST BE
shielded away from power and sensor cables.
Solid Applied Technologies Ltd
Solid House, 48 Montefiore St., Tel Aviv 65201, Israel
Tel(972-3)7101440
www.solidAT.com info@solidgroup.com Fax (972-3)7101405