SPECIFICATIONS
RM Series Card Readers Electrical
The RM Series Card Readers support magnetic stripe, Wiegand, and proximity technologies within a universal housing. The RMx-4000 Multi-Technology reader provides both proximity and contactless smart card technologies within the same housing. Among its many unique features are an LCD integral keypad, and audible feedback. The RM card readers provide two supervised inputs and two outputs when used with the ARM-1.
Autoranging Input .......... 90 to 260 VAC, 47 to 440 HzOutput ..................12 VDC at 3.3 Amp max.Power Consumption ........ Less than 40 Watts typical (12W typical with 4 RMs, 18W with 8 RMs)Auxiliary Hardware ......... Relay contacts rated at 30 V AC/DC 2.5 Amps inductive, 5 Amps non-inductive
Physical
Dimensions (H x W x D) . . . . . . 41.91 x 61.60 x 10.16 cm; (16.5 x 24.25 x 4.0 in)Weight apC/8X and Suppliers of power supply .............10.49 kg (23.31 lbs) apc/8X with Star Coupler
Module and Power Supply ...10.8 kg (24 lbs) Housing ................. 16 AWG metal wall mounted cabinet with tamper switches on door and rear
Input Module (I8)
The Input Module provides eight Class A supervised inputs. A total of eight Input Modules can be connected to one apC/8X panel. Input Modules connect on the reader bus which reduces wiring.
Environmental
Operating Temperature ......0° to 70°C (32° to 158°F)Storage Temperature .......-25° to 85°C (9° to 185°F)Operating and Storage Temperature with apS battery backup ........ 0° to 50°C (32° to 122°F)
Output Module (R8)
The Output Module provides an additional eight outputs. A total of eight Output Modules can be installed on one apC/8X panel. Output Modules connect on the reader bus which reduces wiring.
Regulatory
Compliance ..............FCC Class BCertifications ..............CE, UL 294, UL 1076
apS Advanced Power System
apS is a stand-alone power supply for apC/8X. apS can be used in place of the standard apC/8X power supply and as a backup power supply providing up to 34 amp-hours of uninterrupted battery backup power for apC/8X and the readers connected to it. The power supply connects directly to the power input of apC/8X. apS provides the AC fail and low battery indicators to the apC/8X.
Configuration Options
MODULEMAXIMUM NUMBER OFMODULES PER UNITREADER PORTSREADERSINPUTSOUTPUTS
StandardapC/8X 1 1 RS-4858 Bus8 Class A Supervised8OptionalStar Coupler >
1 18 RS-4858 Star or Bus8 Unsupervised8WPSC >
1 1 (set of 2 modules)8 Star8 Class A SupervisedMini Star Coupler >
1 18 Star or BusI/32 >
3 132 Class A SupervisedR/48 >
3 248 or 96Input Module (I8)88 x 8 Class A SupervisedOutput Module (R8)88 x 8RM Reader82 Class A Supervised8 x 2 >
2 RM-482 Class A Supervised8 x 2 >
2 RM-4E82 Class A Supervised8 x 2 >
2 (1) Either a Star Coupler, WPSC, or Mini Star Coupler can be installed on one apC/8X. (2) Output requires the ARM-1. (3) The I/32 and R/48 can still be used but are no longer sold