| | | MULTIFUNCTION SAFETY UNITS | | 27 | | |
| | | |
| | | |
| | | Note: An internal circuit monitors disparity between the two mute input channels. If the inputs do not switch within 10 sees. of each other the SyStem will go into a lockout condition Terminals B5/B6 and B7/B8 - dual channel emergency stop circuit - Connect one channel of the machines emergency stop circuit between terminals B5 and B6 and the second channel between terminals B7 and B8. | | |
| | | |
| | | Note: An internal circuit monitors for short circuits and switching disparity between the two input channels. If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition. This configuration meets the requirements for 'control reliability' and cannot be used in a single channel configuration. | | |
| | | |
| | | Important, if the emergency stop inputs are not used; it is necessary to link terminals B5 to B6 and terminals B7 to B8. If not the safety output switches will not energise. Terminals B9 and B11 - 24V DC supply - Additional + 24V DC outputs for connecting to the light curtains etc. Terminals B10 and B12 - 0V DC supply - Additional 0V DC outputs for connecting to the light curtains etc. | | |
| | | |
| | | 1000 PLUS SERIES | | |
| | | |
| | | | | | | | | | | | | | |