| | | Autotuned, microprocessor based digital controller PID control function, 2- and 3-point control function Measuring inputs: 1 - Resistance thermometer: Pt 100 - Semiconductor: PTC / NTC - Thermocouples: J, K, S - Voltage signals: 0...50 mV, 0 (12)...60 mV - Norm signals: 0 (4)...20 mA, 0 (1)...5 V 0 (2)...10 V Outputs: max. 2, up to 2 x contr. output resp. 2 x alarm outputs possible - Relay: SPDT 8 A / 3 A / 250 VAC - SSR drive: 8 VDC / 8 mA Displays: 4-digits, 7-segment LEDs 1-line Process value: red, 14 mm high Trend display shift index (3 LEDs) | | Autotuned, microprocessor based digital controller PID control function, 2- and 3-point control function Measuring inputs: 1 - Resistance thermometer: Pt 100 - Semiconductor: PTC / NTC - Thermocouples: J, K, S - Voltage signals: 0...50 mV, 0 (12)...60 mV - Norm signals: 0 (4)...20 mA, 0 (1)... 5 V 0 (2)...10 V Outputs: max. 3, up to 2 x contr. output resp. 2 x alarm outputs possible - Relay: SPDT 8 A / 3 A / 250 VAC - SSR drive: 8 VDC / 8 mA Displays: 4-digits, 7-segment LEDs - TLK 48: 1-line Process value: red, 12 mm high Trend display shift index (3 LEDs) - TLK 49: 2-lines Process value: red, 7 mm high Set value: green, 7 mm high Resolution: -1999 ... 9999 digits - Resistance thermometer: 1/1or1/10 - Thermocouples: 1/1 - Norm signals: free scalable, free setting of decimal point Temperature units: °C, °F Accuracy: ± 0.5 % FS ± 1 digit Transmitter supply: 10 VDC / 20 mA | | |
| | | - Norm signals: 0...20 mA, 4...20 mA 0...10V Outputs: max. 2, up to 2 x contr. output resp. 1 x alarm outputs possible - Relay: SPST 5 A / 2 A / 250 VAC - SSR drive: 6 VDC / 15 mA Displays: 4-digits, 7-segment LEDs 1-line Process value: red, 12 mm high | | |
| | | Resolution: -1999 ... 7000 digits - Resistance thermometer: 1/1or1/10 - Thermocouples: 1/1 - Norm signals: free scalable, decimal point 1/1 or 1/10 Temperature units: °C, °F Accuracy: ± 0.5 % FS ± 1 digit Transmitter supply: 12 VDC / 25 mA | | | Resolution: -999 ... 7000 digits - Resistance thermometer: 1/1 or 1/10 - Thermocouples: 1/1 - Norm signals: free scalable, decimal point 1/1 or 1/10 Temperature units: °C, °F Accuracy: ±0.5%FS±1digit | | |
| | | Dimensions: (W x H x D) - TLK 72: 72 x 72 x 97 mm - TLK 96:96 x 96 x 73 mm Power supply: | | Dimensions: (W x H x D) 48 x48 x 98 mm | | Dimensions: (WxHxD) 48 x 24 x 100 mm Power supply: - 24 VAC/DC, ± 10%, 50/60 Hz - 90...240 VAC, ± 10%, 50/60 Hz | | |