| | | Design Weight Wetted parts materials • Measuring cell • Process connection • Gasket Process connection | | |
| | | Technical specifications SITRANS P pressure transmitter, Z series for gage pressure | | |
| | | 0.2 kg (= 0.44 lb) | | |
| | | |
| | | |
| | | Mode of operation Measuring principle Input Measured variable Measured range | | |
| | | Al2O3 - 96% Brass, mat. No. 2.0402 Viton Male thread G1/B female thread G1/8B | | |
| | | Thin-film strain gage | | |
| | | |
| | | Realtlve pressure 0 to 16 bar g (0 to 232 psl g) or 0 to 25 bar g (0 to 363 psl g) | | |
| | | |
| | | |
| | | |
| | | Terminal voltage on pressure transmitter • For current output Certificate and approvals Classification according to pressure equipment directive (DRGL97/23/EC) | | |
| | | |
| | | Output Current output signal Measuring accuracy Error in measurement (at 25 °C (77 °F), including conformity error hysteresis and repeatability) Response time Tgg Long-term drift • Start of scale • Measured span Influence of ambient temperature • Start of scale • Measured span Rated conditions Medium conditions • Process temperature Degree of protection to EN 60529 Ambient conditions • Ambient temperature • Storage temperature | | |
| | | 4 ... 20 mA To EN 60770-1 0.5% of full-scale value-typical < 0.1 s 0.3% of full-scale value/year - typical 0.3% of full-scale value/year - typical | | |
| | | 10 to 36 VDC | | |
| | | |
| | | For gases of fluid group 1 and liquids of fluid 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) | | |
| | | |
| | | |
| | | Dimensional drawings | | |
| | | |
| | | |
| | | -112 (4.4)- | | |
| | | 0.3%/10 K (0.3%/10 K) of full-scale value - typical 0.3%/10 K (0.3%/10 K) of full-scale value - typical | | |
| | | |
| | | (0.8)1 1 ^ | | |
| | | |
| | | te | | |
| | | |
| | | |
| | | -30 ... +120 °C (-22 ... +248 °F) IP65 -25 ... 85 °C (-13 ... +185 °F) -50 ... 100 °C (-58 ... +212 °F) | | |
| | | SW27 M16x1,5 | | |
| | | |
| | | Schematics | | |
| | | |
| | | |
| | | l0 Output current UB Power supply RL Load Connections: 1 (+UB) 2 (-UB) | | |
| | | ft | | |
| | | ¡71 D_ | | |
| | | |
| | | -U- | | |
| | | |
| | | |
| | | |
| | | | | |
| | | |
| | | ■ Selection and Ordering data Order No. Order code | | |
| | | | | | | | | | | SITRANS P pressure transmitters, Z series for pressure | D) 7MF1562 - ■■■ 00 | | | | | 2-wire system, characteristic rising | | | | | | | | | | | | |
| | | |
| | | |
| | | Measured range Max. working pressure | | |
| | | |
| | | | | | | | | | | 0 ... 16 bar g (0 ... 232 psi g) 32 bar g (464 psi g) | 3CB | | | | | 0 ... 25 bar g (0 ... 363 psi g) 64 bar g (928 psi g) | 3CD | | | | | Other version for measuring range > 1 bar g (> 14.5 psi g), add Order code and plain text: | 9AA | H1 Y | | | | Measuring range: ... to ... bar g (psi g) | | | | | | | | | | | | |
| | | |
| | | D) Subject to export regulations AL: N, ECCN: EAR99H. | | |
| | | |
| | | Siemens FI 01 • 2009^ 2/5 | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |