© Siemens AG 2007
SITRANS P measuring instruments for pressure
Transmitters for gage pressure for the paper industry
DS III series with PMC connectio
I Technical specifications
2
SITRANS P, DS III series for gage pressure with PMC connection for the paper industry
HART
PROFIBUS PA or FOUNDATION Fieldbus
Input
Measured variable
Gage pressure
Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure
Span
0.01 ... 1 bar g (0.145 ... 14.5 psi g)
Max. perm. test pres­sure
6 bar g (87 psi g)
Nominal measuring range
1 bar g (14.5 psi g)
Max. perm. test pres­sure
6 bar g
(87 psi g)
0.04 ... 4 bar g (0.58 ... 58 psi g)
10 bar g (145 psi g)
4 bar g (58 psi g)
10 bar g
(145 psi g)
0.16 ... 16 bar g (2.23 ... 232 psi g)
32 bar g (464 psi g)
16 bar g (232 psi g)
32 bar g (464 psi g)
Lower measuring limit
• Measuring cell with silicone oil filling
100 mbar a (1.45 psi a)
Upper measuring limit
100% of max. span
Output
Output signal
4 ... 20 mA
Digital PROFIBUS PA or FOUNDATION Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA
-
Load
• Without HART communication
RB < (UH - 10.5 V)/0.023 A in £2, Uh : Power supply in V
-
• With HART communication
RB = 230 ... 500 £2 (SIMATIC PDM) or
RB = 230 ... 1100 £2 (HART Communicator)
-
Physical bus
-
IEC 61158-2
With polarity reversal protection
-
Yes
Accuracy
To EN 60770-1
Reference conditions
Increasing characteristic, start-of-scale value 0 bar, stainless steel industrial seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F)) r: Span ratio (r = max. span/set span)
Error in measurement and fixed-point setting (including hysteresis and repeatability)
• Linear characteristic
< 0,075%
-r < 10
< (0.0029 ■ r + 0.071)%
- 10 < r < 30
< (0.0045 ■ r + 0.071)%
- 30 < r < 100
< (0.005 ■ r + 0.05)%
Long-term drift (temperature change ± 30 °C (± 54 °F))
< (0.25 ■ r)% every 5 years
< 0.25% every 5 years
Influence of ambient temperature
•at -10 ... +60 °C (14 ... 140 °F)
< (0.08 ■ r + 0.1)%
< 0,3%
• at -40 ... -10 °C and +60 ... +85 °C (-40 ... +14 °F and 140 ... 185 °F)
< (0.1 ■ r + 0.15)%/10 K
< 0.25%/10 K
Influence of medium temperature
• Temperature difference between medium temperature and ambient temperature
3 mbar/10 K (0.04 psi/10 K)
Influence of mounting position
< 0.1 mbar g (0.00145 psi g) per 10° inclination
Measured Value Resolution
-
3 ■ 10-5 of nominal measuring range
Siemens FI 01 • 2008
2/47
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-222
pdf-page pdf di En 2008-10-42-14