| | | © Siemens AG 2007 | | |
| | | |
| | | SITRANS P measuring instruments for pressure Transmitters for gage, absolute and differential pressure, flow and level | | |
| | | |
| | | S III series jr differential pressure and | | |
| | | flow | | |
| | | |
| | | |
| | | SITRANS P, DS III series, for differential pressure and flow | | |
| | | |
| | | HART | | | | |
| | | |
| | | Certificate and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) PN 32/160 (MWP 464/2320 psi) PN 420 (MWP 6092 psi) Explosion protection • Intrinsic safety "i" - Identification - Permissible ambient temperature - Connection | | |
| | | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3, paragraph 3 (sound engineering practice) For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of Article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TUV Nord. | | |
| | | |
| | | PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 | | |
| | | |
| | | -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °f) temperature class T5; -40 ... +60 °C (-40 ... +140 °f) temperature class T6 | | |
| | | |
| | | To certified Intrinsically-safe circuits with maximum values: U = 30 V, /, = 100 mA, P = 750 mW; R = 300 Q L , = 0.4 mH, C, = 6 nF
| | Uo = 17.5 V, /o = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, /o = 250 mA, Po = 1.2 W L , = 7 |xH, C = 1.1 nF | | |
| | | |
| | | - Effective internal Inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature - Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection | | |
| | | |
| | | PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °f) temperature class T6 | | |
| | | |
| | | To circuits with values: UH = 10.5 ... 45 V DC | | To circuits with values: Uh = 9 ... 32 V DC | | |
| | | |
| | | PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C -40 ... +85 °C (-40 ... +185 °F) 120 °C (248 °F) | | |
| | | |
| | | To certified intrinsically-safe circuits with maximum values: U = 30 V, / = 100 mA, P = 750 mW, R = 300 Q L , = 0.4 mH, C = 6 nF | | FISCO supply unit: Uo = 17.5 V, /o = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, /o = 250 mA, Po = 1.2 W L , = 7 |xH, C = 1.1 nF | | |
| | | |
| | | - Effective internal inductance/capacitance • Dust explosion protection for zone 21/22 - Identification - Connection • Type of protection "n" (zone 2) - Identification • Explosion protection to FM - Identification (XP/DIP) or (IS); (NI) • Explosion protection to CSA - Identification (XP/DIP) or (IS) | | |
| | | |
| | | PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 °C | | |
| | | |
| | | To circuits with values: Uh = 10.5 ... 45 V DC: Pmax = 1.2 W | | To circuits with values: Uh = 9 ... 32 V DC; Pmax = 1.2 W | | |
| | | |
| | | | | |
| | | TÜV 01 ATEX 1696 X
| | Planned | | |
| | | |
| | | Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III | | |
| | | |
| | | |
| | | 2/102 | | |
| | | Siemens FI 01 • 2008 | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |