SITRANS P measuring instruments for pressure Transmitters for gage, absolu^^^gf^fg
SITRANS P, DS III series, for differential pressure and flow
2
HART
PROFIBUS PA or FOUNDATION Fieldbus
• Square-root characteristic (flow 25 ... 50%)
< 0,2
-r < 10
< 0,2%
-
- 10 < r < 30
< 0,4%
-
Long-term drift (temperature change ± 30 °C (± 54 °F))
< (0.25 ■ r)% every 5 years
static pressure max. 70 bar g (1015 psi g)
< (0.25% every 5 years
static pressure max. 70 bar g (1015 psi g)
• 20 mbar (0.29 psi)-measuring cell
< (0.2 ■ r) per year
< 0.2 per year
Influence of ambient temperature
•at -10 ... +60 °C (14 ... 140 °F)
< (0.08 ■ r + 0.1)%
< 0,3%
• at -40 ... -10 °C and +60 ... +85 °C (-40 ... +14 °F and 140 ... 185 °F)
< (0.1 ■ r + 0.15)%/10 K
(Twice the value with 20-mbar (0.29 psi)
measuring cell)
< 0.25%/10 K
Influence of static pressure
• on the zero point
< (0.15 ■ r)% per 100 bar (1450 psi)
< 0.15% je 100 bar (1450 psi)
- 20 mbar (0.29 psi)-measuring cell
< (0.15 ■ r)% per 32 bar (464 psi)
< 0.15% je 32 bar (464 psi)
• on the span
< 0.2% je 100 bar (1450 psi)
-
- 20 mbar (0.29 psi)-measuring cell
< 0.2% je 32 bar (464 psi)
-
Measured Value Resolution
-
3 ■ 10-5 of nominal measuring range
Rated operating conditions
Degree of protection (to EN 60529)
IP65
Process temperature
• Measuring cell with silicone oil filling
-40 ... +100 °C (-40 ... +212 °F)
• Measuring cell with inert filling liquid
-20 ... +100 °C (-4 ... +212 °F)
• In conjunction with dust explosion protec­tion
-20 ... +60 °C (-4 ... +140 °F)
Ambient conditions
• Ambient temperature
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Permissible
• Electromagnetic compatibility
- Emitted interference and interference immunity
To EN 61326 and NAMUR NE 21
Design
Weight (without options)
= 4.5 kg (= 9.9 lb)
Housing material
Poor in copper die-cast aluminium, GD-AlSi12 or stainless steel precision casting, mat. No. 1.4408
Wetted parts materials
Industrial seal diaphragm
Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold
Measuring cell filling
Silicone oil or inert filling liquid (max. 160 bar (2320 psi g) with oxygen measurement)
Process connection
Female thread !4-18 NPT and flange connection with mounting thread M10 to DIN 19213 or 7/16-20 UNF to EN 61518
Power supply Uh
Supplied through bus
Terminal voltage on industrial transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
-
Separate 24 V power supply necessary
-
No
Bus voltage
• Not Ex
-
9 ...32 V
• With intrinsically-safe operation
-
9 ...24 V
Current consumption
• Basic current (max.)
-
12.5 mA
• Startup current < basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) avail.
-
Yes
Siemens FI 01 • 2008
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 101 p.101
page 102 p.102
page 103 p.103
page 104 p.104
page 105 p.105
page 106 p.106
page 107 p.107
page 108 p.108
page 109 p.109
page 110 p.110
page 111 p.111
page 112 p.112
page 113 p.113
page 114 p.114
page 115 p.115
page 116 p.116
page 117 p.117
page 118 p.118
page 119 p.119
page 120 p.120
page 121 p.121
page 122 p.122
page 123 p.123
page 124 p.124
page 125 p.125
page 126 p.126
page 127 p.127
page 128 p.128
page 129 p.129
page 130 p.130
page 131 p.131
page 132 p.132
page 133 p.133
page 134 p.134
page 135 p.135
page 136 p.136
page 137 p.137
page 138 p.138
page 139 p.139
page 140 p.140
page 141 p.141
page 142 p.142
page 143 p.143
page 144 p.144
page 145 p.145
page 146 p.146
page 147 p.147
page 148 p.148
page 149 p.149
page 150 p.150
Pages:
1-50
51-100
101-150
151-200
201-222
pdf-page pdf di En 2008-10-41-07