SITRANS L Level instruments

Point level measurement - Capacitance switches

Pointek CLS300 5/32

â– 

Technical specifications
Design •Material (enclosure) Powder-coated aluminum with gasket•Degree of Protection Standard: Type 4/NEMA 4/IP65Optional: Type 4/NEMA 4/IP68•Cable inlet 2 x M20x1.5 thread (option: 2 x ½” NPT conduit entry including 1plugged entry), digital version has optional PROFIBUS connec- tor (Note: all specifications listed below apply to Standard and Digital ver-sions unless otherwise noted) Mode of operation Controls and industrial displays (CLS300 Standard) Measuring principleInverse frequency shift capaci-tive level detection •Displays 3 LEDs, for adjustment control, output status and power supply•Potentiometers 2 potentiometers for time delay and sensitivity•Switches 5 Dip switches for delay on/off, fail-safe high/low, time delay test/adjust, high/low sensitivity Input Measured variableChange in picoFarad (pF) Output Output signal (CLS300 Standard) •Relay output 1 SPDT Form C relay-Max. contact voltage •30 V DC •250 V AC -Max. contact current •5A (DC) •8A (AC) -Max. switching capacity •150 W (DC) -Max. switching capacity •2000 VA (AC) -Time delay (ON and/or OFF) 1 to 60 s•Solid-state output -Output Galvanically isolated-Protection Against reversed polarity (bipolar)-Max. switching voltage •30 V (DC) •30 V peak (AC) -Max. load current 82 mA-Voltage drop < 1 V, typical at 50 mA-Time delay (pre or post switch-ing) 1 to 60 sOutput signal (CLS300 Digital) Controls and displays (CLS300 Digital) •Local display LCD•Configuration •Locally, using 3 button keypad (for standalone operation) •Remotely, using SIMATIC PDM (for installation on a network) Power supply (CLS300 Standard)

5

•Supply 12 to 250 V AC/DC, 50/60 Hz, gal-vanically isolated•Current consumption 2 W Power supply (CLS300 Digital) •Bus voltage •Standard: 12 to 30 V DC •Intrinsically Safe: 12 to 24 V DC •Current consumption 12.5 mA Certificates and approvals (CLS300 Standard) •General Purpose CE, CSA, FM•Dust Ignition Proof (Intrinsically Safe probe circuit) •CSA/FM Class II and III, Div. 1, Groups E, F, G T4 •ATEX II 1/2D T 100 ºC •Explosion Proof (Intrinsically Safe probe circuit) •CSA/FM Class I, Div. 1, Groups A, B, C, D T4 •ATEX II 1/2G EEx d [ia] IIC T6 to T1 •Marine Lloyd’s Register of Shipping, Cat-egories ENV1, ENV2, and ENV5•Overfill Protection WHG (Germany)•Others •SIL/IEC61508 Declaration of Conformity [SIL 2 (overspill)] •Pattern Approval (China) •C-TICK (Australia) •Solid-state output(CLS300 Digital) -Output Galvanically isolated-Protection Against reversed polarity (bipolar)-Max. switching voltage •30 V (DC) •30 V peak (AC) -Max. load current 82 mA-Voltage drop < 1 V, typical at 50 mA-Time delay (ON and/or OFF) Programmable by user•Fail-safe mode Min. or max.•Connection Removable terminal block, max. 2.5 mm² (0.09") Certificates and approvals (CLS300 Digital) •General Purpose CE, CSA, FM•Dust Ignition Proof •CSA/FM Class II and III, Div. 1, Groups E, F, G T4 or T6 Accuracy Resolution-Min. sensitivity (pF) 1% change in actual capacitance-Max. temperature error 0.2% of actual capacitance value Rated operating conditions
1) Installation conditions LocationIndoor/outdoorAmbient conditions
3) •ATEX II 1/2D 2D T100 °C •Explosion Proof/Dust Ignition Proof (Intrinsically Safe probe circuit) •CSA/FM Class I, II and III, Div. I, Groups A, B, C, D, E, F, G T4 •ATEX II 1/2GD EEx d [ia] IIC T6 to T1 T100 °C •Intrinsically Safe •CSA/FM Class I, II and III, Div. 1, Groups A, B, C, D, E, F, G T4 or T6 •Ambient temperature -40 to +85 °C (-40 to +185 °F)•Pressure range
2) -1 to 35 bar g (-14.6 to 511 psi g)Medium conditions Liquids, bulk solids, slurries and interfaces, and applications with viscous materials•Relative dielectric constant
3) ε r Min. 1.5•Temperature range (probe) -Standard version -40 to +200 °C (-40 to +392 °F)-High-temperature version -40 to +400 °C (-40 to +752 °F) •ATEX II 1G 1D 1/2D EEx ia IIC T6 to T4 T100 °C
3) •Marine Lloyd’s Register of Shipping, Cat-egories ENV1, ENV2, and ENV5•Others •Pattern Approval (China) •C-TICK (Australia) Siemens FI 01 · 2008
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-242
pdf-page pdf di En 2008-10-41-11