SITRANS L Level instruments
Continuous measurement - Ultrasonic controllers
MultiRanger 100/200
5/101 â–
Dimensional drawings
â–
Schematics
See note 1DC version
Relays shown in released state DISCRETEINPUTS 5
Notes
1. Use 2-core copper wire, twisted, with shield, for expansion up to 365 m (1200 ft.).Route cable in grounded metal conduit, separate from other cables.2. Verify that all system components are installed in accordance with instructions.3. Connect all cable shields to the MultiRanger Shield Connections.Avoid differentialground potentials by not connecting cable shields to ground (earth) anywhere else.4. Keep exposed conductors on shielded cables as short as possible to reduce noiseon the line caused by stray transmissions and noise pickup. MultiRanger connections MultiRanger dimensions Siemens FI 01 · 2008 >