Text version of the page
© Siemens AG 2007
SITRANS F flowmeters
SITRANS F
■ Overview
Criteria for selection of flowmeter
Each method for measuring flow has specific properties, and each flow measuring point is characterized by specific require­ments. The table shown below compares the properties of the various measuring instruments and thus provides assistance in selection of the optimum device.
This section of the field device catalog includes the following in­struments for measuring flow:
• Electromagnetic
• Coriolis mass flow
• Ultrasonic
• Variable area meter
• Orifice plate
• Flap
• Rotary-piston meters and professional drum meters
To measure concentration in binary mixtures, it is possible to evaluate the sound velocity measurements of the ultrasonic flow method. The SITRANS F has been specially developed for use with alcohol/water mixtures.
Measuring principle
Electromagnetic
Coriolis
Ultrasonic
Orifice plate
Rotary-piston meter
Variable area meter
Medium
Liquid (conductive)
Liquid or gas
Liquid
Liquid, vapor, gas
Liquid
Liquid or gas
Nominal diameter
DN 2 ... 2000 (0.08" ... 78")
1.5 ... 150 mm
(0.06" . 6")
DN 50 ... DN 4000 (2" ... 160")
DN 10 ... 1000
(0.4" . 40")
DN 15 ... 80
e/2-... 3")
DN 10 . 100 (0.4" . 4")
G/" ... G3"
Temperature range
°C (°F)
-40 ... +200 (-40 ... +392)
-50 ... +180
(-58 . +356)
-200 ... +250
(-328 ... +482)
-200 . +500 (-328 . +932)
-30 . +300 (-22 . +572)
-20 . +300 (-4 . +572)
Max. pressure
bar (psi)
160 (2320), optional higher
Up to 410 (Up to 5950)
40 (580)
430 (6235)
315 (4569)
63 (914)
40 (580)
Accuracy
%
± 0.25 or ± 0.5
± 0.1 or ± 0.15
± 0.5 ... ± 2
± 0.5 ... ± 2
±0.2 ... ±0.5
± 2
Repeatability
%
0.1 . 0.2
0.05
0.2
0.5
0.005
0.5
Dynamic response
1:100
1:100
1:100
1:6
1:10
1:10
Start-of-scale value
m/s (ft/s)
0 (0)
0 (0)
0.1 (0.33)
Ra > 500
0.3 (0.98)
0.2
Full-scale value
Re < 108
• For liquids
m/s (ft/s)
0.25 . 10 (0.825 . 33)
10 (32.8)
10 (32.8)
3
3
3.5 (11.4)
• For vapors/gas­es
m/s (ft/s)
Approx. 300
(1000)
50/25 (164/82)
60 (197)
Measured values
• Volume flow
• Sound velocity
• Sound ampli­tude
• Density
• Mass flow
• Bidirectional measurement
Use
• For custody transfer
• As batching system
• In viscosity range
mPa-s (cp)
0.1 . 100,000
(0.1 ... 100,000)
0 ... 100,000 (0 ... 100,000)
0 ... 350
(0 ... 350)
0 . 10
(0 . 10)
0.3 . 350,000
(0.3 ... 350,000)
0.5 . 100
(0.5 ... 100)
Mains
Mains or battery
2-wire
non
non
4/8 Siemens FI 01 • 2008
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-250
251-300
301-350
351-388
pdf-page pdf di En 2008-10-42-14