Catalogue Siemens - Electropneumatic positioners
www.siemens.com/processautomation
print switch display
Page / 24
Make a request   
SIEMENS Process Instrumentation - 164675, 2631, 3075
/ 24
See other catalogues for SIEMENS Process Instrumentation
Text version of the page
© Siemens AG 2007
Electropneumatic positioners
SIPART PS2
hnical specifications SIPART PS2
SIPART PS2
Basic device without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
with EEx ia/ib protection
Basic device
with EEx n protection
3-/4-wire device (terminals 2/4 and 6/8) (6DR52.. and 6DR53..)
• Power supply UH
• Current consumption IH
• Internal capacitance C,
• Internal inductance L,
• For connection to power circuits with
18 ... 35 V DC
(UH - 7.5 V)/2.4 kfl [mA]
18 ... 35 V DC
(UH - 7.5 V)/2.4 kfl [mA]
18... 30 V DC
(UH - 7.5 V)/2.4 kfl [mA]
< 22 nF
< 0.12 mH
intrinsically safe Uo < 30 V DC Ik < 100 mA P < 1 W
18 ... 30 V DC
(UH - 7.5 V)/2.4 k£2 [mA]
U, < 30 V DC I, < 100 mA
Current input Iw
Rated signal range
0/4 ... 20 mA
0/4 ... 20 mA
0/4 ... 20 mA
0/4 ... 20 mA
Load voltage at 20 mA
< 0.2 V (corresponds to 10 Q)
< 0.2 V (corresponds to 10 Q)
< 1 V (corresponds to 50 Q)
< 1 V (corresponds to
50 Q)
Internal capacitance C,
-
-
< 22 nF
-
Internal inductance (L,)
-
-
< 0.12 mH
-
For connection to power circuits with
intrinsically safe Uo < 30 V DC Ik < 100 mA
P < 1 W
U < 30 V DC I, < 100 mA
between UH and Iw
between UH and Iw
between UH and IW (2 intrinsically safe cir­cuits)
between UH and IW
Test voltage
840 V DC (1 s)
840 V DC (1 s)
840 V DC (1 s)
840 V DC (1 s)
Connections
• Electric
Screw terminals 2.5 AWG28-12
Screw terminals 2.5
AWG28-12
Screw terminals 2.5
AWG28-12
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or 1/2-14 NPT
EEx d certified cable gland M20x1.5,
1-14 NPT or M25 x 1.5
Cable gland M20 x 1.5 or /-14 NPT
Cable gland M20 x 1.5 or /-14 NPT
• Pneumatic
Female thread G/ DIN EN ISO 228-1 or /-18
NPT
Female thread G/ DIN
EN ISO 228-1 or /-18
NPT
Female thread G/ DIN
EN ISO 228-1 or /-18
NPT
Female thread G/ DIN EN ISO 228-1 or /-18
NPT
External position sensor (potentiometer or NCS; as option)
•Uo
-
-
< 5 V
< 5V
•Io
-
-
< 75 mA
< 75 mA
•Is
-
-
<160 mA
<160 mA
•Po
-
-
<120 mW
<120 mW
Maximum permissible external capaci­tance Co
-
-
< 1 |xF
< 1 | F
Maximum permissible external induc­tance Lo
-
-
< 1 mH
< 1 mH
Siemens FI 01 • 2008
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
pdf-page pdf di En 2008-10-42-14