© Siemens AG 2007
Electropneumatic positioners
SIPART PS2
Technical specifications all versions
• Noise (digitally controlled)
to DIN EN 60068-2-64/08.95
10 ... 200 Hz; 1 (m/s2)2/Hz
(3.28 (ft/s2)2/Hz)
200 ... 500 Hz; 0.3 (m/s2)2/Hz
(0.98 (ft/s2)2/Hz)
4 hours/axis
< 30 m/s2 (< 98.4 ft/s2) without res­onance sharpness
■ Technical specifications
SIPART PS2 (all versions)
General data
Travel range (linear actuators)
Angle of rotation (part-turn actuators)
Installation
• On linear actuators
3 ... 130 mm (0.12 ... 5.12 inch) (angle of feedback shaft 16 ... 90°)
30 ... 100°
• Recommended continuous duty range of the complete fitting
Weight, basic device
• Plastic casing
• Metal casing, aluminium
• Metal casing, stainless steel
• Metal casing EEx d version
Dimensions
Approx. 0.9 kg (1.98 lb) Approx. 1.3 kg (2.86 lb) Approx. 3.9 kg (8.58 lb) Approx. 5.2 kg (11.46 lb)
See Dimensional drawings
To DIN EN 60721-3-4
1K5, but -40 ... +80 °C (1K5, but -40 ... +176 °F)
2K4, but -40 ... +80 °C (2K4, but -40 ... +176 °F)
4K3, but -30 ... +80 °C3) (4K3, but -22 ... +176 °F)
Using attachment set 6DR4004-8V and where necessary with an additional lever arm 6DR4004-8L on actuators accord­ing to IEC 534-6 (NAMUR) with ribs, bars or flat face
Using attachment set 6DR4004-8D on actuators with mounting plane according to VDI/VDE 3845 and DIN 3337: The required mounting console has to be provided on the actuator side; shaft with groove and female thread M6
Climate class 4
• Storage1)
•Transport^
• Operation2)
■ On part-turn actuators
Certificate and approvals
Classification according to pres­sure equipment directive (DRGL 97/23/EC)
Controller
• Five-point switch
• Dead zone
- dEbA = Auto
- dEbA = 0.1 ... 10%
• Scan time
• Resolution
• Transmission error
• Temperature effect Cycle time
• 20 mA/HART device
• PA device
• FF device
Binary input BE1 (terminals 9/10; electrically connected to the basic device)
Degree of protection CE marking
For gases of fluid group 1, com­plies with requirements of article 3, paragraph 3 (sound engineering practice SEP)
Self-adjusting
Self-adjusting or can be set as fixed value
Self-adjusting or can be set as fixed value
Pneumatic data
Power supply
• Pressure
Air quality to ISO 8573-1
• Solid particle size and density
• Pressure dew point
• Oil content Unthrottled flow
• Inlet air valve (ventilate actuator)4)
- 2 bar (29 psi)
- 4 bar (58 psi)
- 6 bar (87 psi)
• Outlet air valve (ventilate actuator)4)
- 2 bar (29 psi)
- 4 bar (58 psi)
- 6 bar (87 psi)
Valve leakage Throttle ratio
Power consumption in the controlled state
Types of actuators
• In plastic casing
• In aluminium casing
• In flameproof casing
• In stainless steel casing
Compressed air, nitrogen or cleaned natural gas
1.4 ... 7 bar (20.3 ... 101.5 psi): Sufficiently greater than max. drive pressure (actuating pressure)
10 ms
< 0.05%
< 0.2%
< 0.1%/10 K (< 0.1%/18 °F)
20 ms 60 ms
60 ms (min. loop time)
Suitable only for floating contact; max. contact load < 5 mA with 3 V
IP66 to EN 60 529/NEMA 4x
Conformity as regards EMC Direc­tive 89/336 EC in accordance with the following standards
EN 61326/A1 Appendix A.1 and NAMUR NE21 August 98
Class 2
Class 2 (min. 20 K (36 °F) below ambient temperature)
Class 2
4.1 Nm3/h (18.1 USgpm) 7.1 Nm3/h (31.3 USgpm)
9.8 Nm3/h (43.1 USgpm)
8.2 Nm3/h (36.1 USgpm)
13.7 Nm3/h (60.3 USgpm) 19.2 Nm3/h (84.5 USgpm)
< 6-10-4 Nm3/h (0.0026 USgpm) Adjustable up to ~ : 1
< 3.6-10-2 Nm3/h (0.158 USgpm)
EMC requirements
Material
• Housing
- 6DR5..0-... (plastic)
- 6DR5..1-... (metal)
- 6DR5..2-... (stainless steel)
- 6DR5..5-... (metal, pressure-proof)
• Pressure gauge block Vibration resistance
• Harmonic oscillations (sine-wave) according to DIN EN 60062-2-6/05.96
Glass-fiber-reinforced Macrolon GD AISi12
Austenitic stainless steel mat. No. 1.4581
GK AISi12
Aluminium AIMgSi, anodized
Single-action and double-action Single-action
Single-action and double-action Single-action and double-action
1:
During commissioning at < 0 °C (< 32 °F) make sure that the valves are flushed long enough with the dry medium.
At < -10 °C (14 °F) the display refresh rate of the LCD is limited. Only T4 is permissible when using Iy module.
-25 ... +75 °C (-13 ... +167 °F) for 6DR55..-0G..., 6DR56..-0G..., 6DR55..-0D... and 6DR56..-0D...
With EEx d version (6DR5..5-...) the values are reduced by approx. 20%
2)
3.5 mm (0.14 inch), 2 ... 27 Hz 3 cycles/axis
98.1 m/s2 (321.84 ft/s2), 27 ... 300 Hz, 3 cycles/axis
150 m/s2 (492 ft/s2), 6 ms,
1000 shocks/axis
3)
4)
■ Bumping (half-sine) to DIN EN 60068-2-29/03.95
Siemens FI 01 • 2008
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24