Answers for industry. BETA Low-Voltage Circuit Protection Characteristic curves for fuses and information on configuration for catalog ET B1 Catalog Add-On ET B1 AO • 2009

Open the catalog to page 1
Add-On - ET B1 AO - 2

ALPHA Distribution Boards and Terminal Blocks Order No.: pdf only: (E86060-K8210-A101-A9-7600) ET A1 ALPHA SIMBOX Small Distribution Boards· SIMBOX 63, SIMBOX LC, SIMBOX WP · ALPHA 160 - DIN Wall-Mounted Distribution Boards· ALPHA 400 - DIN Wall-Mounted Distribution Boards· ALPHA 630 - DIN Floor-Mounted Distribution Boards· ALPHA AS Modular Distribution Boards· ALPHA Modular Distribution Boards up to1600 A · ALPHA 400-ZS Meter Cabinets· ALPHA BOX · ALPHA 8HP Molded-Plastic Distribution Systems· Planning and Configuration· ALPHA FIX terminal blocks: Screw Terminals, Terminals with...

Open the catalog to page 2
Add-On - ET B1 AO - 3

BETA Low-Voltage Circuit Protection Catalog Add-On ET B1 AO · 2009 Characteristic curves for fuses and information on configuration for catalog ET B1 Replaces: Catalog ET B1 AO · 2008, Characteristic curves for catalog ET B1 The products in this catalog can be also found in the electronic catalog CA 01. Order No.: E86060-D4001-A510-C7-7600 (DVD) Contact your local Siemens representative © Siemens AG 2009 The products and systems listed in this catalog are developed and manufactured using a VDE-approved quality management system according to EN ISO 9001:2000. Low-Voltage Fuse Systems SITOR...

Open the catalog to page 3
Add-On - ET B1 AO - 4

Siemens ET B1 AO 2 · 2009, Characteristic curves for fuses

Open the catalog to page 4
Add-On - ET B1 AO - 5

3 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3/2 Introduction 3/5 NEOZED fuse systems 3/7 DIAZED fuse systems 3/13 Cylindrical fuse systems 3/19 Class CC fuse systems 3/21 LV HRC fuse links

Open the catalog to page 5
Add-On - ET B1 AO - 6

Introduction 3/2 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3 ¡Overview Rated voltage Un The rated voltage is the designated voltage of the fuse and and is used to determine its test conditions and operational voltage limits. For LV HRC and SITOR fuse links, the rated voltage is always the r.m.s. value of an AC voltage. In the case of NEOZED and DIAZED fuse links, a distinction is made between AC and DC voltage values. Rated current In The rated current of a fuse link is the designated current of the fuse link and is the current up to which it can be continuously loaded under...

Open the catalog to page 6
Add-On - ET B1 AO - 7

Introduction Siemens ET B1 AO · 2009, Characteristic curves for fuses 3/3 The following operational classes are included in the product range: gG (DIN VDE/IEC) = Full range cable and line protection aM (DIN VDE/IEC) = Partial range switching device protection aR (DIN VDE/IEC) = Partial range semiconductor protection gR (DIN VDE/IEC) = Full range semiconductor protection gS (DIN VDE/IEC) = Full range semiconductor protection and cable and line protection Quick(DIN VDE/IEC/CEE) = Full range cable and line protection Slow (DIN VDE) = Full range cable and line protection Characteristic curves...

Open the catalog to page 7
Add-On - ET B1 AO - 8

Introduction 3/4 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3 Current limitation As well as a failsafe rated breaking capacity, the current-limiting effect of a fuse link is of key importance for the cost effectiveness of a system. In the event of short-circuit breaking by a fuse, the breaking current continues to flow through the network until the fuse link is switched off. However, the breaking current is limited by the system impedance. The simultaneous melting of all the bottlenecks of a fuse element produce a sequence of tiny partial arcs that ensure a fast...

Open the catalog to page 8
Add-On - ET B1 AO - 9

NEOZED fuse systems Siemens ET B1 AO · 2009, Characteristic curves for fuses 3/5 ¡Characteristic curves Series 5SE2 Size: D01, D02, D03 Operational class: gG Rated voltage: 400 V AC/250 V DC Rated current: 2 ... 100 A Time/current characteristic curves diagram Current limitation diagram $ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component Melting I2t values diagram Table see page 3/6.

Open the catalog to page 9
Add-On - ET B1 AO - 12

DIAZED fuse systems 3/8 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3 Series 5SA1 Size: E16 Characteristic: quick Rated voltage: 500 V AC/500 V DC Rated current: 2 ... 25 A Time/current characteristic curves diagram Current limitation diagram $ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component Melting I2t values diagram Type In Pv A W 5SA1 11 2 1.5 5SA1 21 4 1.9 5SA1 31 6 2.7 5SA1 51 10 3.4 5SA1 61 16 3.7 5SA1 71 20 4.4 5SA1 81 25 4.9

Open the catalog to page 12
Add-On - ET B1 AO - 20

Cylindrical fuse systems 3/16 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3 Series 3NW6 30.-1 Size: 8 mm × 32 mm Operational class: gG Rated voltage: 400 V AC Rated current: 2 ... 20 A Time/current characteristic curves diagram Current limitation diagram $ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component Melting I2t values diagram Type In Pv DJ I2ts I2ta 1 ms 400 V AC A W K A2s A2s 3NW6 302-1 2 2 27 1.6 6 3NW6 304-1 4 1.5 19 5 21 3NW6 301-1 6 1.5 20.5 48 85 3NW6 303-1 10 0.7 15 230 530 3NW6 305-1 16 1.1 29 600 1400 3NW6...

Open the catalog to page 20
Add-On - ET B1 AO - 21

Cylindrical fuse systems Siemens ET B1 AO · 2009, Characteristic curves for fuses 3/17 Series 3NW8 Size: 10 mm × 38 mm 14 mm × 51 mm 22 mm × 58 mm Operational class: aM Rated voltage: 500 V AC, 400 V AC (3NW8 120-1, 3NW8 230-1) Rated current: 0,5 ... 100 A Time/current characteristic curves diagram Current limitation diagram $ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component Melting I2t values diagram

Open the catalog to page 21
Add-On - ET B1 AO - 22

Cylindrical fuse systems 3/18 Siemens ET B1 AO · 2009, Characteristic curves for fuses 3 Series 3NW8 Size: 10 mm × 38 mm 14 mm × 51 mm 22 mm × 58 mm Operational class: aM Rated voltage: 500 V AC 400 V AC (3NW8 120-1, 3NW8 230-1) Rated current: 0.5 ... 100 A Time/current characteristic curves diagram Current limitation diagram $ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component Melting I2t values diagram

Open the catalog to page 22