VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 1

VTdrive - Harmonic Distortion from Variable Speed Drives

Open the catalog to page 1
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 2

Introduction to Harmonics Symptoms Expected Harmonics from VFD’s Harmonic Resonance Understanding IEEE519-1992 Harmonic Solutions for VFD’s

Open the catalog to page 2
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 3

Harmonic Distortion • Harmonic problems are becoming more apparent because more harmonic producing equipment is being applied to power systems – VFD’s – Electronic Ballasts – UPS • Additionally, in many cases, these electronic based devices can also be more sensitive to harmonics Effective Grounding Harmonic Solutions Surge Solutions Voltage Variation Solutions

Open the catalog to page 3
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 4

problem unless they are a Horizontal 2500 microseconds/digision Vertical 500 Uolts/division Urns: Preu=610.7, Min=605.5, Max=605.5 - Uorst Inp= H Upk, 0 deg

Open the catalog to page 4
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 5

Harmonic Symptoms/Concerns • Equipment Failure and Misoperation – – – – – Notching (electronic control malfunctioning, regulator misoperation) Overheating/Failure (transformers, motors, cables/neutral) Nuisance Operation (fuses, breakers, PC lock-ups) Insulation deterioration Capacitor resonance / failure • Economic Considerations – Oversizing neutrals, transformers, generators – Losses/Inefficiencies/PF Penalties – Inconsistent meter reading • Application of Power Factor Correction Capacitors • Other Issues – Metering – do you really have a problem? – Marketing hype – buy my product! –...

Open the catalog to page 5
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 6

Expected Harmonics Source Typical Harmonics* Arcing Devices Transformer Energization * Generally, magnitude decreases as harmonic order increases

Open the catalog to page 6
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 7

Harmonic Spectrum Harmonic magnitude (per unit) 0.2 0.14 • Normal VFD Harmonic Spectrum – Lower harmonic orders have the higher magnitudes – Magnitudes should decline as the harmonic order increases

Open the catalog to page 7
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 8

Harmonic Spectrum spectrum exhibits abnormal magnitudes, harmonic resonance interaction with Power Factor Correction

Open the catalog to page 8
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 9

Power Factor Correction and Harmonics Parallel Resonant Frequencies for Various Capacitor Sizes Harmonic Order • PFCC's change the resonant frequency of the distribution system - Depends on the size of the caps and the impedance of the • Can magnify any existing harmonics

Open the catalog to page 9
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 10

Power Factor Correction and Harmonics HARMONIC NUMBER Reactors can be added to the PFCC bank to create a tuned filter - Tuned to a 'non-characteristic' harmonic (i.e. 4.7th) Becomes a sink for 5th harmonic currents

Open the catalog to page 10
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 11

IEEE 519 - 1992 • It is currently the only recognized industry standard in North America for setting harmonic limits (voltage and current) • Designed to limit utility harmonics as well as customer harmonic contribution to the utility grid • Standard ONLY applies to the Point of Common Coupling (PCC) – The point where the utility connects to multiple customers – If a utility transformer is provided, the PCC is most likely on the LINE side of the transformer IEEE 519 is widely misunderstood and misapplied in the industry

Open the catalog to page 11
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 12

IEEE 519 – Point of Common Coupling (PCC) Possible POA’s (Customer Side) (Utility Side) Only place that IEEE 519 applies ??? = Linear loads for % current distortion dilution

Open the catalog to page 12
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 13

Harmonic Calculators File Help General System Special Applications XFMR Filter Total HP of Linear Load

Open the catalog to page 13
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 14

Which came first?….. Voltage Distortion Current Distortion • In this case…the Egg! – Current distortion causes Voltage distortion – Voltage distortion is created by pulling distorted current through an impedance – Amount of voltage distortion depends on: • System impedance • Amount of distorted current pulled through the impedance • If either increases, VTHD will increase

Open the catalog to page 14
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 15

IEEE 519 - Voltage Distortion Limits IEEE 519 sets limits for both Voltage distortion and Current Harmonic Voltage Distortion Limits

Open the catalog to page 15
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 16

IEEE 519 - Current Distortion Limits Not THD Harmonic Current Distortion Limits (Ih and TDD) in % of IL (≤ 69kV) • Current distortion limits are dependent on the “stiffness” of the source (Isc/IL) – A stiffer source has lower impedance = more distortion allowed – A softer source (i.e. generator) has higher impedance = less distortion allowed • Current distortion limits are typically much more difficult to reach than Voltage distortion limits

Open the catalog to page 16
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 17

THD vs. TDD • THD(I)= Total Harmonic Current Distortion – Measured distortion on actual instantaneous current flowing – “Sinewave Quality Factor” • Lower the % THD, the closer the current waveform is to a true sinewave – Not used anywhere in IEEE 519 THD = 80% Is this acceptable? Depends on system full load, % linear load, etc.

Open the catalog to page 17
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 18

THD vs. TDD • TDD(I) = Total Current Demand Distortion – Calculated harmonic current distortion against the full load (demand) level of the electrical system Full load of the system – The greater the amount of Linear load, the less of an issue the current distortion becomes – Looks at the full capacity of the system • If non-linear loads are a small % of the full system current demand, the TDD is less

Open the catalog to page 18
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 19

TDD vs THD Example: With Harmonic Correction Full load * As the load decreases, TDD decreases while THD(I) increases. Equal at full load

Open the catalog to page 19
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 20

Harmonic Solutions for VFD’s Oversized Generator Active Filter Blocking Filter Isolation Transformer Tuned Filter Phase Shift Transformers

Open the catalog to page 20
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 21

Harmonic Solutions for VFD’s * Line Reactors • K-Rated / Drive Isolation Transformers • Harmonic Mitigating Transformers/Phase Shifting • 12-Pulse Converter • 18-Pulse Converter • Passive Parallel Tuned Filters • Passive Series Tuned Filters • Active Filters • Active Rectifier (Regenerative VFD’s)

Open the catalog to page 21
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 22

Line Reactors • Line Reactor = Inductor • An inductor slows down the rate of rise of current. Current • Impedance of an inductor increases as frequency increases • Reactors have more impedance the higher the harmonic order

Open the catalog to page 22
VTdrive - Harmonic Distortion from Variable Speed Drives(VSD) - 23

Effect of Drive Line Reactors

Open the catalog to page 23