Text version of the page
1 Specifications
Table 1: Sensor specifications (at 22°C and p
absolute = 966 mbar, V
DD = 5.0 V unless otherwise noted). SDP1000-L05 SDP1000-L SDP1000-R SDP2000-L SDP2000-R Unit Parameter
Min Typ Max Min Typ Max Min Typ Max Min Typ Max Min Typ Max -5 125 - 20 500 - 20 500 -100 3500 -100 3500 Pa Measurement range -0.02 0.5 -0.08 2 -0.08 2 -0.4 14 -0.4 14 Inch water Full scale output >
(100 k load) 3.94 4.00 4.06 3.94 4.00 4.06 3.94 4.00 4.06 3.94 4.00 4.06 3.94 4.00 4.06 V Zero Pressure Output 0.247 0.250 0.253 0.247 0.250 0.253 0.238 0.250 0.262 0.247 0.250 0.253 0.238 0.250 0.262 V Corresponding Offset - 0.1 0 + 0.1 - 0.4 0 + 0.4 - 2.8 0 + 2.8 Pa >
(3) Power supply >
(see Tab 4) 4.75 5.00 5.25 4.75 5.00 5.25 4.75 5.00 5.25 4.75 5.00 5.25 4.75 5 5.25 V Accuracy 0.2 0.3 0.1 0.2 0.2 0.3 0.1 0.2 0.2 0.3 % FS >
(1)(2) [0°C < T < 50°C] (also see Figure 1) 1.5 2 1 1.5 1 1.5 1 1.5 1 1.5 % m.v. >
(1) Repeatability 0.3 0.5 0.3 0.5 0.3 0.5 0.3 0.5 0.3 0.5 % m.v. >
(1) Offset stability 0 0.1 0 0.1 0 0.3 0 0.3 0 0.5 Pa / year Temp. variation of zero pressure output -3 +3 -3 +3 -30 +30 -3 +3 -30 +30 mV >
[0°C < T < 50°C] - 0.1 + 0.1 - 0.4 + 0.4 - 2.8 + 2.8 Pa Temperature error of span 0.8 1.0 0.2 0.25 0.30 0.40 0.2 0.25 0.30 0.40 % FS >
(1)(2) [T < 0°C or T > 50°C] 1.50 3.00 1.50 3.00 1.50 3.00 1.50 3.00 1.50 3.00 % m.v. >
(1) Resolution < 30% FS (1) 0.05 0.1 0.2 0.05 0.1 0.2 0.2 0.5 1 0.2 0.5 1 Pa >
Resolution 30..70% FS (1) 0.05 0.1 0.2 1.5 2.2 3 1.5 2.2 3 8 11 14 8 11 14 Pa 0.2 0.5 1.5 0.2 0.5 1.5 1 2.5 8 1 2.5 8 Pa >
Resolution > 70% FS (1) (1) FS = full scale or span, m.v. = measured value, i.e. reading, whichever value is bigger >
(2) FS = full scale or span, i.e. for the SDP1000 it is 500 Pa (2 “H2O), for the SDP2000 it is 3500 Pa (14 “H2O) >
(3) See 2.2 Voltage Output formula for conversion >
(1) SDP1000 / SDP2000 around 23°C (2) SDP1000 / SDP2000 between 0°…50°C (3) Typical membrane based sensor with 1.5% FS error between 10°…40°C (1) SDP1000-L (2,3) Membrane based sensors
offset drift/year [Pa] ± error [ % of measured value] (1) (2) (3) 012345
678910
0102030405060708090100 01234567
01234 1 2 3
differential pressure [% full scale]
repeatability [Pa]
Figure 1: Accuracy (includes errors caused by offset, linearity, hysteresis and repeatability) of the SDP1000 -L (1), (2) compared with typical membrane sensors (3). Figure 2: Max. repeatability and offset drift/year of the SDP1000-L (1) compared with two typical membrane based sensors (2,3). www.sensirion.com v 2.7 June 2005 2/8