K-LINE Compact converters 6,2 mm normalized case TECHNICALFEATURES
GENERALINFORMATIONS DIMENSIONS
K109PT K109PT1000 K109TC K109UI K109S K109SH K107A K107B K107USB K-SUPPLY
Power supply range*Industrial bridge voltage supply 19,2.. 30 VdcBus connectors (K-BUS) can be snapped onto 35 mm DIN guide rail according to EN 60175 Wire section 0,2..2,5 mm
2 Wire stripping 8 mm Power on side terminals Yes Hot swapping Yes Max current consumption 21..25 mA(24 Vdc) Consumption without load at 25°C 7,5 mA
Pt100
industrial converter Pt1000 converter
Thermocouple converter withsettable threshold
Galvanic isolator analogue converter V / I converter with active output Current shunt / V-I converter RS485/RS485 serial repeater RS232/RS485 serial converter RS485/USB asyncronous serial converter K-BUS power supply for K-line modules >
Max power consumption 500 mOhm A/D conversion 14 bit
3 way galvanic isolator conver-ting Pt100 temperature in stan-
dard current/voltage signal. 3 way galvanic isolator conver-ting Pt1000 temperature in standard current/voltagesignal. 3 way galvanic isolator for ther-mocouple input. Settable acti-
ve output, auxiliary switchingrelay output, exceeding threl-hold. 3 way galvanic isolator for cur-rent or voltage conversion.
Passive input and active out-put. 3 way galvanic isolator for vol-tage or current conversion.
Active output and floatingpower supply. 3 way galvanic isolator for the con-version of a current shunt value into
a current or voltage signal.Programmable scales. RS485 serial repeater, 3 ways isolation, automatic flow control. RS232B / RS485 serial converter, halfduplex, , 3 ways isolation, automatic
flow control. RS485/USB serial converter withspecific drivers. Isolated RS485 /
USB interface. Redundant power supply modulewith overvoltages protection and dif-
ferential mode filter. Rejection 50 o 60 Hz (programmable) Settings DIPSwitch Filter Insertable Dimensions 93,1 x 6,2 x 102,5 mm Isolation 1,5 KV (50 Hz, 1 min)
GENERALDATA
Isolation technique Digital (optocoupler) Processing Floating point 32 bit
Channels 1 input, 1 output 1 input, 1 output 1 input, 2 outputs 1 input, 1 output 1 input, 1 output 1 input, 1 output 1 input, 1 output 1 input, 1 output 1 input, 1 output 2 inputs, 1 output >
Colour Black
Precision 0,1 % 0,1 % 0,1 % 0,1 % 0,1 % 0,1 % >
Case material PBT
Thermal driftLED < 100 ppm/K
Fault / alarm < 120 ppm/K Fault / alarm < 120 ppm/K Fault / alarm
Threshold setting Static relay output status < 120 ppm/K Fault / alarm < 120 ppm/K Fault / alarm < 120 ppm/K Fault / alarm >
Weight 45 g
Power ON Data OK Inverted connection Power ON Data OK Inverted connection Power ON RS485 Rx RS485 Tx Input 1 switch on threshold Input 1 switch on threshold Alternate / inverted polarity of inputs >
Operating temperature -20..+65 °C Storage temperature -40..+85 °C Humidity 10..90 % non condensing Connection Clamp terminals and/or bus
Power supply 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc 19,2..30 Vdc By USB port of the PC >
Protection degreeConformity IP20CE, EN 50081-2, EN 50082-2, EN 61010-1, EN
Isolation 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1,5 kV (50 Hz, 1 min) 1.500 V (USB / RS485) Dimensions
Communication 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm 93,1 x 6,2 x 102,5 mm Timing automatic handshake Baud rate: 1.200..115.200 bps
Terminal
Flow communication stop 93,1 x 6,2 x 102,5 mm Timing automatic handshake Baud rate: 1.200..115.200 bps
Terminal
Flow communication stop 93,1 x 6,2 x 102,5 mm Baud rate: 1.200..250 kbps RS485 line terminal 93,1 x 6,2 x 102,5 mm >
60742
* Except for K107USB and K-SUPPLY >
CONNECTION AND INSTALLING
Special functions Programmable fault and cut-off
Insertable filter Programmable fault and cut-off
Insertable filter Programmable fault and cut-off
Insertable filter Settable rejection 50 60 Hz Square root extraction
Standard
industrial tanks linearisation Signal inversion
Programmable cut-off Programmable scales on demand Square root extraction
Standard tanks linearisation Signal inversion
Programmable cut-off Auxiliary power supply on 3 terminal Compliance to USB 1.1 and 2.0 Plug&play for WIN 98, 2000 and XP Multiple connection on the same PC
CD Driver Differential mode filter Integrated protection against overvoltages Connection with redundant power supply, to several bus and parallel inputs >
CAGE CLAMPCONNECTION K-BUS
Instruction sequenzerequires stripping of
cables, opening block
spring with a screwdri-
ver, inserting the cable
in the hole.
Module is screw holdon the top of DIN
guide, then it has to
pressed to the bottom
for the final clip-on
fastening. Each expandable con-nector K-BUS allows
inserting two modules.
K-BUS are inserted on
guide setting them to
the top and round
them at the bottom.
blocks 17..20 V, max current 25 mA >
INPUT DATA
Type PT100 Pt100 (IEC 751 / EN 60751 ITS90)
Range: -150..+150 °C
Minimum span: 50 °C Power on transmitter 900 ΅A Connection technique: 2, 3, 4 wires
Max conductor resistance: 20 β¦ PT1000 Pt1000 (EN 60751/A2 - ITS90)
Range: -200..+210 °C
Minimum span: 30°C Power on transmitter < 350 ΅A Connection technique: 2, 3, 4 wires
Max conductor resistance 50 β¦ THERMOCOUPLE Type: J, K, E, N, S, R, B, T(ITS-90 standard) Temperature range: minimum span 100°C Impedance: 10 M β¦
VOLTAGE Range: 0..10 / 2..10 / 0..5 / 1..5 / 0..15 / 0..30 V reversed Impedance: 110 k β¦(10 V), 325 k β¦(30 V) VOLTAGE Range: 0..10 / 10..0 / 0..5 / 1..5 V
Impedance: 110 k⦠CURRENT VOLTAGE SERIAL Half duplex (31 nodes, teminal, protection up to 30 Vdc) SERIAL RS232B, protection up to 30 Vdc SERIAL USB interface, USB standard 1.0 / 2.0 compliance, USB Aand MINI USB B connectors POWER SUPPLY 2 inputs with shared negative terminal
Pass-through each input can be accessed by 2 pairs of terminals Max current per terminal: 4 A Positive inputs protected by an external
industrial fuse of recommended sizing Range: 0..20 / 4..20 mA Impedance: 35 β¦ Shunt: from ±100 mV up to ±500 mV Range: 0..20 / 4..20 mA
Impedance: 35 β¦ CURRENT Cold junction (semiconductor,
ADC 13 bit, precision 1,4 °C, time upgrade 10s) Absolute value Max voltage ±32 V Max voltage:±32 V
Current clamp self powered: 400 mβ¦ Max voltage:±30 V
Current clamp self powered: 400 m⦠>
OUTPUT DATA
Type VOLTAGE Range: 0..10 / 10..0 / 0..5 / 1..5 V
Max voltage: overrange 10,25 V; fault 10,5 V, available 12 V Min load resistance: 2 k β¦ VOLTAGE Range: 0..10 / 10..0 / 0..5 / 1..5 V
Max voltage: overrange 10,25 V; fault 10,5 V, available 12 V Min load resistance: 2 k⦠VOLTAGE Range: 0..10 / 10..0 / 0..5 / 1..5 V
Min load resistance: 2 k⦠VOLTAGE Range: 0..10 / 2..10 / 0..5 / 1..5 V
Min load resistance: 2 k⦠VOLTAGE Range: 0..10 / 2..10 / 0..5 / 1..5 V
Min load resistance: 2 k⦠TENSIONE Range: 0..10 / 2..10 / 0..5 / 1..5 V
Min load resistance: 2 k⦠SERIAL RS485 Half duplex (31 nodes, teminal, protection up to 30 Vdc) SERIAL RS485 Half duplex (31 nodes, terminal, protection up to 30 Vdc) SERIAL RS 485, max 31 nodes, spring-cage terminal block POWER SUPPLY Max voltage drop: 300 mV >
INSERTING MODULE ON DIN GUIDE EXTRACTING MODULE ON DIN GUIDE
Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max current: overrange 20,5 mA; fault 21 mA, protection 25 mA Max load resistance: 500 β¦ Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max current: overrange 20,5 mA; fault 21 mA, protection 25 mA Max load resistance: 500 β¦ CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max load resistance: 500 β¦ Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max load resistance: 500 β¦
Protection: 25 mA Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max load resistance: 500 β¦
Protection: 25 mA Range: 4..20 / 20..4 / 0..20 / 20..0 mA Max load resistance: 500 β¦ Protection: 25 mA >
Pry downward on the
latch with a screwdri-
ver, then round the
module to the top.
Protection: 25 mA Protection: 25 mA Static relay auxiliary output Nominal voltage: 24 Vac/dc
Current: 60 mA
Overvoltage protection: 50 V
Settable alarm threshold / hysteresys Response time (10-90%) < 50 ms (without filter)
< 200 ms (with filter) < 50 ms (without filter)
< 200 ms (with filter) < 40 ms (without filter)
< 40/88 ms (with filter) < 40 ms (without filter)
< 40/88 ms (with filter) D/Aconversion 1 mV, 2 ΅A 1 mV, 2 ΅A 1 mV, 2 ΅A 1 mV, 2 ΅A 1 mV, 2 ΅A Resolution >