Standards:IEC/EN 60204-1EN 60947-5-3EN 954-1BG-GS-ET-14 BG-GS-ET-20 Stop category0 Control category:3 Start conditions:automatic or start button Start-up test:no / yes Enclosure:glass-fibre reinforced thermoplastic Mounting:snaps onto standard DIN rail to EN 50022 Termination:screw terminals •Control Category 3 to EN 954-1•Classification PDF-M to EN 60947-5-3 incombination with BNS safety sensors•1 enabling path
•Enable delay time can be modified•Monitoring of BNS range magnetic safety sensors•Can be changed from NO/NC to NC/NC contact combination•Cross-wire monitoring with NO-NC contact combination•ISD Integral System Diagnostics•Available for various operating voltages•Connection of input expander possible Cable section:max. 4 mm >
2 (incl. conductor ferrules)Protection class:terminals IP 20 enclosure IP 40 to EN 60529U >
e :AES 2135.1/2136.1: 110 VACAES 2135.2/2136.2: 230 VAC AES 2135.3/2136.3: 24 VAC I >
e :0.2 A Power consumption:5 W Feedback circuit:no Monitored inputs1 NC / 1 NO Input resistance:approx. 2 k >
Ω
to ground Input signal „1“:10 ... 30 VDC Input signal „0“:0 ... 2 VDC Max. cable length:1000 m of 1.5 mm >
2 conductor Enabling contacts:1 enabling path Utilisation category:AC-15, DC-13I >
e /U >
e :2 A / 250 VAC 2 A / 24 VDC Contact load capacity:max. 250 VAC, max. 4 A (cos >
Ï•
= 1) Max.
industrial fuse rating:4 A gL/gG D-fuse Signalling output:– Function display:LED (ISD) EMC rating:conforming to EMC Directive Max. switching frequency:3 Hz Overvoltage category:II to DIN VDE 0110 Degree of pollution:3 to DIN VDE 0110 Resistance to vibration:10 ... 55 Hz / amplitude 0.35 mm, ±15 % Resistance to shock:30 g / 11 ms Ambient temperature:0 °C … + 55 ºC Storage and transport temperature:– 25 °C … + 70 ºC Dimensions:55 x 75 x 110 mmNote:Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. Approvals >
H C D
Ordering details
AES 213 >
➀âž
No. Replace Description >
➀
5Without start-up test6With start-up test >
âž
.1110 VAC
.2230 VAC.324 VAC >
1-116