Inductive proximity switches / DC 4-wire IFL Ø 20 mm Technical data Contact variants
Standards:IEC/EN 60947-5-2 VDE 0660-208S IFL 10-200L-11P >
BN WHBK L+L n :10 mm, non-embeddableSwitching element function:A: normally open contact and B: normally closed contact (antivalent)Switching output:P: 4-wire DCU >
BU NO+NC – b :10 ... 60 VDCI >
e :400 mAI >
:approx. 5.5 mA (24 V)U >
d :approx. 1.5 V (400 mA)Protection circuit:wrong polarity and inductive interference protection, on request: short-circuit and overload proof(Index -1665-1) Ie = 300 mA, Ud = approx. 1 V (300 mA)Ambient temperature:– 25 °C … + 70 ºCSwitching frequency f:approx. 350 HzProtection class:IP 67 to EN 60529Protection class:II, >
Ø20 LED 7932000 X Material:housing and clamp H 20: thermoplasticConnection:cable LiYY 4 x 0.25 mm •
Thermoplastic enclosure• Design Ø 20 mm• Cable
• DC 4-wire• Clamp H 20 is included in delivery, see accessories >
2 , length 2 m >
IFL Ø 20 mm Technical data Contact variants
Standards:IEC/EN 60947-5-2 VDE 0660-208S IFL 10-200L-11STP >
1 24 L+L n :10 mm, non-embeddableSwitching element function:A: normally open contact and B: normally closed contact (antivalent)Switching output:P: 4-wire DCU >
3 NO+NC – b :10 ... 60 VDCI >
e :400 mAI >
:approx. 5.5 mA (24 V)U >
d :approx. 1.5 V (400 mA)Protection circuit:wrong polarity and inductive interference protection, on request:short-circuit and overload proof (Index -1665-1) Ie = 300 mA, Ud = approx. 1 V (300 mA)Ambient temperature:– 25 °C … + 70 ºCSwitching frequency f:approx. 350 HzProtection class:IP 67 to EN 60529Protection class:II, >
LED Ø20 M18x1 91 X Material:housing and clamp H 20: thermoplasticConnection:Plug-in connector M18 x 1 • Thermoplastic enclosure• Design Ø 20 mm• Plug-in connector• DC 4-wire• Clamp H 20 is included in delivery, see accessories >
2-50