AS-Interface Safety at Work ASM Technical data
Standards:EN 50295, EN 60947-5-1, EN 61496-1 (1997), IEC/EN 60204-1, EN 954-1 Control category:4 Enclosure:Polyamide PA 66, black Mounting:snaps onto standard DIN rail to EN 50022 Screw terminals:max. 2.5 mm >
2 (incl. conductor ferrules)Protection class:terminals IP 20 enclosure IP 20 to EN 60529 U >
b :24 VDC ±15 % Residual ripple:< 15%Ib:ASM 1-R2: 0.15 A ASM 2-R2/R2: 0.2 A Switch-on peak current:600 mA •Safety monitor•Control Category 4 to EN 954-1
•Monitor for AS-Interface
INDUSTRIAL SAW compatible safety device, i.e.
industrial safety switches, solenoidinterlocks, E-Stop buttons, 2-Hand control,
light grid and
light curtains•AS-Interface connection
•One or two redundant pairs of enabling paths•Additional outputs (transistor, short-circuit proof)•Configurable functions: OR logical element,Start devices, Start-up test•Edge-sensitive start push button•Feedback circuit to monitor external contactors•LEDs to diplay switching conditions•Operating voltage 24 VDC AS-Interface operating voltage:18.5 ... 31.6 V AS-Interface operating current:< 45 mA AS-Interface specification:Profile - Monitor 7.F Configuration interface:RS232: 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits Inputs:1.Y1,1.Y2 Input signal:„Y1, Y2“: le < 10 mA at 24 VDC (opto coupler, high-active)Outputs:ASM 1/R2: 1.13/14,1.23/241 enabling path (redundant);ASM 2-R2/R2: 1.13/14,1.23/24, 2.13/14, 2.23/24 2 enabling paths (redundant) Utilisation category:AC-15, DC-13I >
e /U >
e :3 A / 230 VAC 1 A / 24 VDC Switching voltage:max. 230 VAC I >
the :3 A per output circuit Max.
industrial fuse rating:4 A (slow blow), externalAdditional outputs:transistor outputs, 200 mA total, short-circuit proof-type, positive-switching Switch-on time:< 10 s Response time:< 40 msIndications:AS-Interface: voltage LED green, communication LED red; Enabling paths: LED green, yellow, red EMC rating:conforming to EMC Directive Overvoltage category:III to DIN VDE 0110Resistance to vibration:5 ... 55 Hz / amplitude 0.35 mm ±15 % at the regulation point Resistance to shock:10 g / 16 ms Ambient temperature:– 20 °C … + 60 ºC Storage and transport temperature:– 30 °C … + 70 ºCWeight:ASM 1/R2: approx. 350 g; ASM 2-R2/R2: approx. 450 gNote:Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. Approvals >
H C D
Ordering details Note
ASM >
➀
The
safety monitors ASM 1-R2 and ASM 2-R2/R2 evaluate all transmitted information from eachsafety device on the AS-Interface network. For the safe guarding of different applications variousAS-Interface Safety at Work compatible safety devices are needed, i.e. safety switches,
solenoid
interlocks,
safety sensors, E-stop buttons as well as safe input modules.The AS-Interface Safety at Work can be used in applications up to control category 4 accordingto EN 954-1 with the appropriate safety devices and systems. No. Replace Description >
➀
1-R21 enabling field (redundant)2-R2/R22 enabling fields (redundant) >
5-38