AS-Interface Safety at Work AZ 16 AS Technical data System components

Standards:EN 50295EN 60947-5-1EN 954-1Enclosure:glass-fibre reinforced thermoplastic, self-extinguishingAS-Interface connection type:connector M12 x 1Protection class:IP 67 to EN 60529AS-Interfaceoperating voltage:26.5 ... 31.6 VDC, via AS-Interface, reverse-polarity proofAS-Interface operating current:
Rmin.150 5640 5 Rmin.150 28,3 275,516 Straight actuator AZ 15/16-B1 Flexible actuator AZ 15/16-B2 Flexible actuator AZ 15/16-B6
14 M12M12525,5 408 13930
aa
101611 Rmin.45 ≤ 50 mAspecification:Profile S-0.BIO-Code: 0x0ID-Code: 0xB ID-Code2: 0xEInputs:Contact Status Data bits1 on D0/D1 = dynamic code transmission1 off D0/D1 = static code 002 on D2/D3 = dynamic code transmission2off D2/D3 = static code 00Parameter bits:P0 P3: not usedInput module address:default on address 0, programmable via the AS-Interface Master or Hand-held programming deviceIndications:AS-Interface: voltage LED green, communication LED redEnabling status: LED yellowMechanical life:> 1 million operationsEMC rating:conforming to EMC DirectiveAmbient temperature: 25 C + 60 CStorage and transport temperature: 25 C + 85 C
56 5,5 40 57 15,571882990 27,3 27 Safety switch with separate actuator Integrated AS-Interface interface AS-Interface LED status display AS-Interface M12 connector Address jack (optional) Thermoplastic enclosure Coded actuator Long life Protection class IP 67
16 Rmin.38 5640 Rmin.25 5,5 711 27,3 27 Approvals

H C D

Ordering details Note Ordering details

AZ 16

-AS

➁➂

4123

Straight actuator AZ 15/16-B1 No. Replace Description Flexible actuator AZ 15/16-B2 Flexible actuator AZ 15/16-B6

ST1Connector (middle)ST2Connector (right)ST3Connector (left) M12 connector: Further actuators can be found in the chapter Industrial safety switches with separate actuator, see page 1-8.Actuators must be ordered separately. 1: AS-Interface +2: spare3: AS-Interface 4: spare

No latchingrLatching 30 Nr-2254Latching 5 N

No address jackbAddress jack

5-41

DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
pdf-page pdf di En 2008-10-42-14