AS-Interface Safety at Work
Note
• The installation of different safety areas is
possible with numerous safety monitors
working alongside each other. The maximum
number of safety devices including the safety
monitors may not exceed 31 participants.
• The allocation of the safety devices to one or
more safety monitors is achieved with the
help of the configuration software ”asimon“.
• The wiring diagram shows the safety monitor
ASM E2-R2/R2 with start-pushbuttons and
feedback loops.
• No safety devices are displayed, because
they are installed in the field i.e. on the safety
guards itself. The data connection between
the safety monitor and the decentralised
safety slaves is established via the ASInterface
network.
• For the operation of AS-Interface Safety at
Work system, a standard controller, an ASInterface
Master and AS-Interface power
supply, must be used in the application.
• With the RJ 45 connector the safety monitor
is configured and started up.
• Start push button
A start push button (NO) can optionally be
connected to the ASM. With the guard
door(s) closed, the enabling paths are then
not closed until the start push button has
been operated. If neither start button nor
feedback circuit are required, then no
connections are required to the terminals
(1Y1/2, 2Y1/2).
• Output expander module
For additional contacts by means of more
enabling paths and potential-free indication
contacts an output expander module is
connected to the safety monitor, i.e. to the
internal ASM enabling path. For the control
of the additional outputs the ASM feedback
loop is utilised.
Wiring diagram
L1
AS-i+ AS-i- 1Y1
K1
K2
L+ M FE 1.14 1.24 2.14 2.24 2.14 2.24
2.32 1.13 1.23 2.13
K5 K5
L1 L2 L3 L1 L2 L3
K7 K7
S1 S2
M1 M2
K6 K6 K8 K8
3 3
K3
K4
1Y2
24 V
2Y1 2Y2 1.32 2.23
AS-i+
AS-i-
+ 24 VDC
+ 24 VDC + 24 VDC
0 V N
M N M
RS
232
RJ 45
ASInterface
0 V
Note
Further information and details of the safety
monitor ASM are available on the asimon-
CD-ROM.
Note
The AS-i system limitations according to EN 50295 have to be concidered during the planning,
development and design phase of the AS-i network, especially the max. number of AS-i slaves
and the total „yellow“ cable length (< 100 m without repeater).
For the control of safety outputs and for coupling multiple AS-i networks, other safety monitoring
modules like ASM G2 must be used.
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
|
|